EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Single-Phase Time Overcurrent Protection; Functional Description

Siemens SIPROTEC 4 7UT6 Series
684 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Single-Phase Time Overcurrent Protection
The single-phase time overcurrent protection can be assigned to either of the single-phase measured addi-
tional current inputs of the device. This may be a “normal” input or a high-sensitivity input. In the latter case, a
very sensitive pickup threshold is possible (smallest setting 3 mA at the current input).
The single-phase time overcurrent protection comprises two definite time delayed stages which can be
combined as desired. If only one stage is required, set the other to ∞.
Examples for application are high-impedance differential protection or high-sensitivity tank leakage protec-
tion. These applications are covered in the following subsections.
Functional Description
The measured current is filtered by numerical algorithms. Due to high sensitivity, a particularly narrow band
filter is used.
For the single-phase Ι>>-stage, the current measured at the assigned current input is compared with the
setting value 1Phase I>>. Current above the pickup value is detected and annunciated. When the delay time
T I>> has expired, tripping command is issued. The reset value is approximately 95 % of the pickup value for
currents above Ι
N
. For lower values the dropout ratio is reduced in order to avoid intermittent pickup on
currents near the setting value (e.g. 90 % at 0.2 · Ι
N
).
When high fault current occurs, the current filter can be bypassed in order to achieve a very short tripping
time. This is automatically done when the instantaneous value of the current exceeds the set value Ι>> stage
by at least factor 2 · √2 .
For the single-phase Ι>-stage, the current measured at the assigned current input is compared with the setting
value 1Phase I>. Current above the pickup value is detected and annunciated. When the delay time T I>
has expired, the tripping command is issued. The reset value is approximately 95 % of the pickup value for
currents above Ι
N
. Lower values require a higher hysteresis in order to avoid intermittent pickup on currents
near the pickup value (e.g. 80 % at 0.1 · Ι
N
).
Both stages form a two-stage definite time overcurrent protection (Figure 2-86).
Das Figure 2-87 illustrates the logic diagram for the single-phase overcurrent stage.
[ueb-einph-kennlinie-020926-rei, 1, en_GB]
Figure 2-86 Two-stage tripping characteristic of the single-phase time overcurrent protection
2.7
2.7.1
Functions
2.7 Single-Phase Time Overcurrent Protection
SIPROTEC 4, 7UT6x, Manual 177
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals