EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Page 375

Siemens SIPROTEC 4 7UT6 Series
684 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[webmon-diff-messwertsek-zeig, 1, en_GB]
Figure 3-33 Phasor Diagram of the Secondary Measured Values — Example
Phase angle measurement for measuring location M1 with test current:
Check the phase angle under Measurement values → Secondary → Phase angles of side 1 of the
protected object. All angles are referred to Ι
L1M1
.
φ
L1 M1
≈ 0°
φ
L2 M1
≈ 240°
φ
L3 M1
≈ 120°
If the angles are wrong, reverse polarity or swapped phase connections on measuring location M1 may
be the cause.
Switch off the test source and the protected object (shut down the generator) and earth it.
Re-check the plant connections to the device and the test arrangement and correct them.
Repeat test and re-check the current angles.
Phase angle measurement for measuring location M2 with test current:
Check the phase angle under measurement values → secondary → phase angles of measuring location
M2 of the protected object. All angles are referred to Ι
L1M1
.
Consider that always the currents flowing into the protected object are defined as positive: That means
that, with through-flowing in-phase currents, the currents leaving the protected object at measuring
location M2, have reversed polarity (180° phase displacement) against the corresponding in-flowing
currents at measuring location M1.
Exception: With transverse differential protection, the currents of the corresponding phase have equal
phase!
For clockwise phase rotation and without phase displacement, the angles should be approximately:
φ
L1 M2
≈ 180°
φ
L2 M2
≈ 60°
φ
L3 M2
≈ 300°
When measuring across a power transformer, approximately the values according to Table 3-33.
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7UT6x, Manual 375
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals