Addr. Parameter Function C Setting Options Default Setting Comments
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another
Setting Group
311 UN-PRI SIDE 1 P.System Data
1
0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage
Side 1
312 SN SIDE 1 P.System Data
1
0.20 ..
5000.00 MVA
38.10 MVA Rated Apparent Power of
Transf. Side 1
313 STARPNT SIDE 1 P.System Data
1
Earthed
Isolated
Earthed Starpoint of Side 1 is
314 CONNECTION S1 P.System Data
1
Y
D
Z
Y Transf. Winding Connec-
tion Side 1
321 UN-PRI SIDE 2 P.System Data
1
0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage
Side 2
322 SN SIDE 2 P.System Data
1
0.20 ..
5000.00 MVA
38.10 MVA Rated Apparent Power of
Transf. Side 2
323 STARPNT SIDE 2 P.System Data
1
Earthed
Isolated
Earthed Starpoint of Side 2 is
324 CONNECTION S2 P.System Data
1
Y
D
Z
Y Transf. Winding Connec-
tion Side 2
325 VECTOR GRP S2 P.System Data
1
0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of
Side 2
331 UN-PRI SIDE 3 P.System Data
1
0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage
Side 3
332 SN SIDE 3 P.System Data
1
0.20 ..
5000.00 MVA
10.00 MVA Rated Apparent Power of
Transf. Side 3
333 STARPNT SIDE 3 P.System Data
1
Earthed
Isolated
Earthed Starpoint of Side 3 is
334 CONNECTION S3 P.System Data
1
Y
D
Z
Y Transf. Winding Connec-
tion Side 3