Addr. Parameter Function C Setting Options Default Setting Comments
355 VECTOR GRP S5 P.System Data
1
0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of
Side 5
361 UN GEN/MOTOR P.System Data
1
0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage
Generator/Motor
362 SN GEN/MOTOR P.System Data
1
0.20 ..
5000.00 MVA
70.00 MVA Rated Apparent Power of
the Generator
370 UN BUSBAR P.System Data
1
0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage
Busbar
371 I PRIMARY OP. P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current of Busbar
372 I PRIMARY OP S1 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current Side 1
373 I PRIMARY OP S2 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current Side 2
374 I PRIMARY OP S3 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current Side 3
375 I PRIMARY OP S4 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current Side 4
376 I PRIMARY OP S5 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current Side 5
381 I PRIMARY OP 1 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 1
382 I PRIMARY OP 2 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 2
383 I PRIMARY OP 3 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 3
384 I PRIMARY OP 4 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 4
385 I PRIMARY OP 5 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 5
386 I PRIMARY OP 6 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 6
387 I PRIMARY OP 7 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 7
388 I PRIMARY OP 8 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 8
389 I PRIMARY OP 9 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 9
390 I PRIMARY OP 10 P.System Data
1
1 .. 100000 A 200 A Primary Operating
Current End 10
Functions, Settings, Information
F.2 Settings
552 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016