Addr. Parameter Function C Setting Options Default Setting Comments
1125 PoleOpenCurr.M5 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold Meas.Loc. M5
5A 0.20 .. 5.00 A 0.20 A
1131 PoleOpenCurr I1 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 1
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1132 PoleOpenCurr I2 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 2
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1133 PoleOpenCurr I3 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 3
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1134 PoleOpenCurr I4 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 4
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1135 PoleOpenCurr I5 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 5
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1136 PoleOpenCurr I6 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 6
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1137 PoleOpenCurr I7 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 7
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1138 PoleOpenCurr I8 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 8
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1139 PoleOpenCurr I9 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 9
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1140 PoleOpenCurrI10 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 10
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
1141 PoleOpenCurrI11 P.System Data
2
1A 0.04 .. 1.00 A 0.04 A Pole Open Current
Threshold End 11
5A 0.20 .. 5.00 A 0.20 A
0.1
A
0.004 .. 0.100 A 0.004 A
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7UT6x, Manual 561
C53000-G1176-C230-5, Edition 09.2016