Addr. Parameter Function C Setting Options Default Setting Comments
1702 Start CLP Phase ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C Phase
1703 Start CLP 3I0 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C 3I0
1704 Start CLP Earth ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C Earth
1705 Start CLP Ph 2 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C Phase 2
1706 Start CLP Ph 3 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C Phase 3
1707 Start CLP 3I0 2 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C 3I0 2
1708 Start CLP 3I0 3 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C 3I0 3
1709 Start CLP E 2 ColdLoadPickup No Current
Breaker Contact
No Current Start Condition CLP for
O/C Earth 2
1711 CB Open Time ColdLoadPickup 0 .. 21600 sec 3600 sec Circuit Breaker OPEN
Time
1712 Active Time ColdLoadPickup 1 .. 21600 sec 3600 sec Active Time
1713 Stop Time ColdLoadPickup 1 .. 600 sec; ∞ 600 sec Stop Time
2001 PHASE O/C Phase O/C ON
OFF
Block relay
OFF Phase Time Overcurrent
2002 InRushRest. Ph Phase O/C ON
OFF
OFF InRush Restrained O/C
Phase
2008A MANUAL CLOSE Phase O/C I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
2011 I>> Phase O/C 1A 0.10 .. 35.00 A; ∞ 4.00 A I>> Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
2012 I>> Phase O/C 0.10 .. 35.00 I/InS;
4.00 I/InS I>> Pickup
2013 T I>> Phase O/C 0.00 .. 60.00 sec; ∞ 0.10 sec T I>> Time Delay
2014 I> Phase O/C 1A 0.10 .. 35.00 A; ∞ 2.00 A I> Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
2015 I> Phase O/C 0.10 .. 35.00 I/InS;
2.00 I/InS I> Pickup
2016 T I> Phase O/C 0.00 .. 60.00 sec; ∞ 0.30 sec T I> Time Delay
2021 Ip Phase O/C 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
2022 Ip Phase O/C 0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
2023 T Ip Phase O/C 0.05 .. 3.20 sec; ∞ 0.50 sec T Ip Time Dial
2024 D Ip Phase O/C 0.50 .. 15.00 ; ∞ 5.00 D Ip Time Dial
2025 TOC DROP-OUT Phase O/C Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out character-
istic
Functions, Settings, Information
F.2 Settings
564 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals