Addr. Parameter Function C Setting Options Default Setting Comments
2442 I Max InRr. E Earth O/C 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr.
Rest. O/C Earth
5A 1.50 .. 125.00 A 37.50 A
2511 IE>> Earth O/C 1A 0.05 .. 35.00 A; ∞ 7.00 A IE>> Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
2512 T IE>> Earth O/C 0.00 .. 60.00 sec; ∞ 1.50 sec T IE>> Time Delay
2513 IE> Earth O/C 1A 0.05 .. 35.00 A; ∞ 1.50 A IE> Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
2514 T IE> Earth O/C 0.00 .. 60.00 sec; ∞ 2.00 sec T IE> Time Delay
2521 IEp Earth O/C 1A 0.05 .. 4.00 A 1.00 A IEp Pickup
5A 0.25 .. 20.00 A 5.00 A
2522 T IEp Earth O/C 0.05 .. 3.20 sec; ∞ 0.50 sec T IEp Time Dial
2523 D IEp Earth O/C 0.50 .. 15.00 ; ∞ 5.00 D IEp Time Dial
2701 1Phase O/C 1Phase O/C OFF
ON
Block relay
OFF 1Phase Time Overcurrent
2702 1Phase I>> 1Phase O/C 1A 0.05 .. 35.00 A; ∞ 0.50 A 1Phase O/C I>> Pickup
5A 0.25 .. 175.00 A; ∞ 2.50 A
2703 1Phase I>> 1Phase O/C 0.003 .. 1.500 A; ∞ 0.300 A 1Phase O/C I>> Pickup
2704 T 1Phase I>> 1Phase O/C 0.00 .. 60.00 sec; ∞ 0.10 sec T 1Phase O/C I>> Time
Delay
2705 1Phase I> 1Phase O/C 1A 0.05 .. 35.00 A; ∞ 0.20 A 1Phase O/C I> Pickup
5A 0.25 .. 175.00 A; ∞ 1.00 A
2706 1Phase I> 1Phase O/C 0.003 .. 1.500 A; ∞ 0.100 A 1Phase O/C I> Pickup
2707 T 1Phase I> 1Phase O/C 0.00 .. 60.00 sec; ∞ 0.50 sec T 1Phase O/C I> Time
Delay
2911A FFM U>(min) Supervision 10 .. 100 V 20 V Minimum Voltage
Threshold U>
3001 PHASE O/C Phase O/C 2 ON
OFF
Block relay
OFF Phase Time Overcurrent
3002 InRushRest. Ph Phase O/C 2 ON
OFF
OFF InRush Restrained O/C
Phase
3008A MANUAL CLOSE Phase O/C 2 I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
3011 I>> Phase O/C 2 1A 0.10 .. 35.00 A; ∞ 4.00 A I>> Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
3012 I>> Phase O/C 2 0.10 .. 35.00 I/InS;
4.00 I/InS I>> Pickup
3013 T I>> Phase O/C 2 0.00 .. 60.00 sec; ∞ 0.10 sec T I>> Time Delay
3014 I> Phase O/C 2 1A 0.10 .. 35.00 A; ∞ 2.00 A I> Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
3015 I> Phase O/C 2 0.10 .. 35.00 I/InS;
2.00 I/InS I> Pickup
3016 T I> Phase O/C 2 0.00 .. 60.00 sec; ∞ 0.30 sec T I> Time Delay
3021 Ip Phase O/C 2 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
Functions, Settings, Information