EasyManua.ls Logo

Siemens SIPROTEC 4 7UT6 Series - Page 571

Siemens SIPROTEC 4 7UT6 Series
684 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Addr. Parameter Function C Setting Options Default Setting Comments
3311 I>> Phase O/C 3 1A 0.10 .. 35.00 A; ∞ 10.00 A I>> Pickup
5A 0.50 .. 175.00 A; ∞ 50.00 A
3312 I>> Phase O/C 3 0.10 .. 35.00 I/InS;
10.00 I/InS I>> Pickup
3313 T I>> Phase O/C 3 0.00 .. 60.00 sec; ∞ 0.10 sec T I>> Time Delay
3314 I> Phase O/C 3 1A 0.10 .. 35.00 A; ∞ 4.00 A I> Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
3315 I> Phase O/C 3 0.10 .. 35.00 I/InS;
4.00 I/InS I> Pickup
3316 T I> Phase O/C 3 0.00 .. 60.00 sec; ∞ 0.30 sec T I> Time Delay
3321 Ip Phase O/C 3 1A 0.10 .. 4.00 A 4.00 A Ip Pickup
5A 0.50 .. 20.00 A 20.00 A
3322 Ip Phase O/C 3 0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup
3323 T Ip Phase O/C 3 0.05 .. 3.20 sec; ∞ 0.50 sec T Ip Time Dial
3324 D Ip Phase O/C 3 0.50 .. 15.00 ; ∞ 5.00 D Ip Time Dial
3401 3I0 O/C 3I0 O/C 2 ON
OFF
Block relay
OFF 3I0 Time Overcurrent
3402 InRushRest. 3I0 3I0 O/C 2 ON
OFF
OFF InRush Restrained O/C 3I0
3408A 3I0 MAN. CLOSE 3I0 O/C 2 3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close
Mode
3411 3I0>> 3I0 O/C 2 1A 0.05 .. 35.00 A; ∞ 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; ∞ 5.00 A
3412 3I0>> 3I0 O/C 2 0.05 .. 35.00 I/InS;
1.00 I/InS 3I0>> Pickup
3413 T 3I0>> 3I0 O/C 2 0.00 .. 60.00 sec; ∞ 1.50 sec T 3I0>> Time Delay
3414 3I0> 3I0 O/C 2 1A 0.05 .. 35.00 A; ∞ 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; ∞ 2.00 A
3415 3I0> 3I0 O/C 2 0.05 .. 35.00 I/InS;
0.40 I/InS 3I0> Pickup
3416 T 3I0> 3I0 O/C 2 0.00 .. 60.00 sec; ∞ 2.00 sec T 3I0> Time Delay
3421 3I0p 3I0 O/C 2 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
3422 3I0p 3I0 O/C 2 0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
3423 T 3I0p 3I0 O/C 2 0.05 .. 3.20 sec; ∞ 0.50 sec T 3I0p Time Dial
3424 D 3I0p 3I0 O/C 2 0.50 .. 15.00 ; ∞ 5.00 D 3I0p Time Dial
3425 TOC DROP-OUT 3I0 O/C 2 Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out Character-
istic
3426 IEC CURVE 3I0 O/C 2 Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7UT6x, Manual 571
C53000-G1176-C230-5, Edition 09.2016

Table of Contents

Related product manuals