Addr. Parameter Function C Setting Options Default Setting Comments
9011A RTD 1 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 1: Temperature Stage
1 Pickup
9014 RTD 1 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 1: Temperature Stage
1 Pickup
9015 RTD 1 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 1: Temperature Stage
2 Pickup
9016 RTD 1 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 1: Temperature Stage
2 Pickup
9021A RTD 2 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 2: Temperature Stage
1 Pickup
9024 RTD 2 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 2: Temperature Stage
1 Pickup
9025 RTD 2 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 2: Temperature Stage
2 Pickup
9026 RTD 2 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD 2: Temperature Stage
2 Pickup
9031A RTD 3 TYPE RTD-Box Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION RTD-Box Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD 3: Temperature Stage
1 Pickup
9034 RTD 3 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD 3: Temperature Stage
1 Pickup
9035 RTD 3 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD 3: Temperature Stage
2 Pickup
Functions, Settings, Information