Addr. Parameter Function C Setting Options Default Setting Comments
9123 RTD12 STAGE 1 RTD-Box -50 .. 250 °C; ∞ 100 °C RTD12: Temperature
Stage 1 Pickup
9124 RTD12 STAGE 1 RTD-Box -58 .. 482 °F; ∞ 212 °F RTD12: Temperature
Stage 1 Pickup
9125 RTD12 STAGE 2 RTD-Box -50 .. 250 °C; ∞ 120 °C RTD12: Temperature
Stage 2 Pickup
9126 RTD12 STAGE 2 RTD-Box -58 .. 482 °F; ∞ 248 °F RTD12: Temperature
Stage 2 Pickup
Functions, Settings, Information
F.2 Settings
586 SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016