Addr. Parameter Function C Setting Options Default Setting Comments
261 OP.CYCLES AT Ir P.System Data
1
100 .. 1000000 10000 Switching Cycles at Rated
Normal Current
262 Isc-52 P.System Data
1
10 .. 100000 A 25000 A Rated Short-Circuit
Breaking Current
263 OP.CYCLES Isc P.System Data
1
1 .. 1000 50 Switch. Cycles at Rated
Short-Cir. Curr.
264 Ix EXPONENT P.System Data
1
1.0 .. 3.0 2.0 Exponent for the Ix-
Method
265 Cmd.via control P.System Data
1
(Einstellmöglich-
keiten anwendung-
sabhängig)
none 52 B.Wear: Open Cmd.
via Control Device
266 T 52 BREAKTIME P.System Data
1
1 .. 600 ms 80 ms Breaktime (52 Breaker)
267 T 52 OPENING P.System Data
1
1 .. 500 ms 65 ms Opening Time (52
Breaker)
276 TEMP. UNIT P.System Data
1
Celsius
Fahrenheit
Celsius Unit of temperature
measurement
280 Holmgr. for Σi P.System Data
1
NO
YES
NO Holmgreen-conn. (for fast
sum-i-monit.)
281A Swi.auth.via BI P.System Data
1
NO
YES
OFF
NO Change switch.authority
via binary input
282A Interl.on/offBI P.System Data
1
NO
YES
OFF
NO Interlocking on or off via
binary input
302 CHANGE Change Group Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another
Setting Group
401 WAVEFORM-
TRIGGER
Osc. Fault Rec. Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
402 WAVEFORM DATA Osc. Fault Rec. Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
403 MAX. LENGTH Osc. Fault Rec. 0.30 .. 5.00 sec 2.00 sec Max. length of a Wave-
form Capture Record
404 PRE. TRIG. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior
to Trigger
405 POST REC. TIME Osc. Fault Rec. 0.05 .. 0.50 sec 0.10 sec Captured Waveform after
Event
406 BinIn CAPT.TIME Osc. Fault Rec. 0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary
Input
610 FltDisp.LED/LCD Device, General Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
611 Spont. FltDisp. Device, General YES
NO
NO Spontaneous display of
flt.annunciations
613A 50N/51N/67N w. P.System Data
1
Ignd (measured)
3I0 (calcul.)
Ignd (measured) 50N/51N/67N Ground
Overcurrent with
Functions, Settings, Information
F.2 Settings