Addr. Parameter Function C Setting Options Default Setting Comments
614A OP. QUANTITY 59 P.System Data
1
Vphph
Vph-n
V1
V2
Vphph Opera. Quantity for 59
Overvolt. Prot.
615A OP. QUANTITY 27 P.System Data
1
V1
Vphph
Vph-n
V1 Opera. Quantity for 27
Undervolt. Prot.
617A T103 with 16 MV Device, General YES
NO
OFF
NO T103-transfer limeted to
16 meas. values
625A T MIN LED HOLD Device, General 0 .. 60 min; ∞ 0 min Minimum hold time of
latched LEDs
640 Start image DD Device, General image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 8
image 9
image 10
image 1 Start image Default
Display
700 GOOSE-Stop Device, General YES
NO
NO GOOSE-Stop
1101 FullScaleVolt. P.System Data
2
0.10 .. 800.00 kV 12.00 kV Measurem:FullScale-
Voltage(Equipm.rating)
1102 FullScaleCurr. P.System Data
2
10 .. 50000 A 100 A Measurem:FullScaleCur-
rent(Equipm.rating)
1103 RE/RL P.System Data
2
-0.33 .. 7.00 1.00 Zero seq. compensating
factor RE/RL
1104 XE/XL P.System Data
2
-0.33 .. 7.00 1.00 Zero seq. compensating
factor XE/XL
1105 x' P.System Data
2
1A 0.0050 ..
15.0000 Ω/mi
0.2420 Ω/mi feeder reactance per
mile: x'
5A 0.0010 ..
3.0000 Ω/mi
0.0484 Ω/mi
1106 x' P.System Data
2
1A 0.0050 ..
9.5000 Ω/km
0.1500 Ω/km feeder reactance per km:
x'
5A 0.0010 ..
1.9000 Ω/km
0.0300 Ω/km
1107 I MOTOR START P.System Data
2
1A 0.40 .. 10.00 A 2.50 A Motor Start Current
(Block 49, Start 48)
5A 2.00 .. 50.00 A 12.50 A
1108 P,Q sign P.System Data
2
not reversed
reversed
not reversed P,Q operational measured
values sign
1109 Line angle P.System Data
2
10 .. 89 ° 85 ° Line angle
1110 Line length P.System Data
2
0.1 .. 1000.0 km 100.0 km Line length in kilometer
1111 Line length P.System Data
2
0.1 .. 650.0 Miles 62.1 Miles Line length in miles
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 621
C53000-G1140-C207-8, Edition 08.2016