Addr. Parameter Function C Setting Options Default Setting Comments
3161 α2 red.dir.area Sens. Gnd Fault 1 .. 15 ° 2 ° Alpha2 (reduction direc-
tional area)
3301 INTERM.EF Intermit. EF OFF
ON
OFF Intermittent earth fault
protection
3302 Iie> Intermit. EF 1A 0.05 .. 35.00 A 1.00 A Pick-up value of interm.
E/F stage
5A 0.25 .. 175.00 A 5.00 A
3302 Iie> Intermit. EF 1A 0.05 .. 35.00 A 1.00 A Pick-up value of interm.
E/F stage
5A 0.25 .. 175.00 A 5.00 A
3302 Iie> Intermit. EF 0.005 .. 1.500 A 1.000 A Pick-up value of interm.
E/F stage
3303 T-det.ext. Intermit. EF 0.00 .. 10.00 sec 0.10 sec Detection extension time
3304 T-sum det. Intermit. EF 0.00 .. 100.00 sec 20.00 sec Sum of detection times
3305 T-reset Intermit. EF 1 .. 600 sec 300 sec Reset time
3306 Nos.det. Intermit. EF 2 .. 10 3 No. of det. for start of int.
E/F prot
3401 Dir. Interm. EF Dir. Interm. EF OFF
ON
ON with GF log
Alarm Only
OFF Dir. Intermittent earth
fault protection
3402 Direction Dir. Interm. EF Forward
Reverse
Forward Direction to be protected
3403 No. of pulses Dir. Interm. EF 2 .. 50 5 Pulse no. for detecting
the interm. E/F
3404 Monitoring time Dir. Interm. EF 0.04 .. 10.00 sec 2.00 sec Monitoring time after
pickup detected
3405 Vgnd> / 3V0> Dir. Interm. EF 2.0 .. 100.0 V 20.0 V Vgnd> measured / 3V0>
calculated
3406 Pickup Dir. Interm. EF with Vgnd/3V0>
with oper. dir.
with Vgnd/3V0> Pickup of the function
4001 FCT 46 46 Negative
Seq
OFF
ON
OFF 46 Negative Sequence
Protection
4002 46-1 PICKUP 46 Negative
Seq
1A 0.05 .. 3.00 A 0.10 A 46-1 Pickup
5A 0.25 .. 15.00 A 0.50 A
4003 46-1 DELAY 46 Negative
Seq
0.00 .. 60.00 sec; ∞ 1.50 sec 46-1 Time Delay
4004 46-2 PICKUP 46 Negative
Seq
1A 0.05 .. 3.00 A 0.50 A 46-2 Pickup
5A 0.25 .. 15.00 A 2.50 A
4005 46-2 DELAY 46 Negative
Seq
0.00 .. 60.00 sec; ∞ 1.50 sec 46-2 Time Delay
4006 46 IEC CURVE 46 Negative
Seq
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv. 46 IEC Curve
4007 46 ANSI CURVE 46 Negative
Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. 46 ANSI Curve
4008 46-TOC PICKUP 46 Negative
Seq
1A 0.05 .. 2.00 A 0.90 A 46-TOC Pickup
5A 0.25 .. 10.00 A 4.50 A
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ62/64, Manual 631
C53000-G1140-C207-8, Edition 08.2016