Addr. Parameter Function C Setting Options Default Setting Comments
4009 46-TOC TIMEDIAL 46 Negative
Seq
0.50 .. 15.00 ; ∞ 5.00 46-TOC Time Dial
4010 46-TOC TIMEDIAL 46 Negative
Seq
0.05 .. 3.20 sec; ∞ 0.50 sec 46-TOC Time Dial
4011 46-TOC RESET 46 Negative
Seq
Instantaneous
Disk Emulation
Instantaneous 46-TOC Drop Out
4012A 46 T DROP-OUT 46 Negative
Seq
0.00 .. 60.00 sec 0.00 sec 46 Drop-Out Time Delay
4101 FCT 48 48/66 Motor-
prot
OFF
ON
OFF 48 Startup Time Supervi-
sion for Motors
4102 STARTUP CURRENT 48/66 Motor-
prot
1A 0.50 .. 16.00 A 5.00 A Startup Current
5A 2.50 .. 80.00 A 25.00 A
4103 STARTUP TIME 48/66 Motor-
prot
1.0 .. 180.0 sec 10.0 sec Startup Time
4104 LOCK ROTOR TIME 48/66 Motor-
prot
0.5 .. 180.0 sec; ∞ 2.0 sec Permissible Locked Rotor
Time
4105 STARTUP T WARM 48/66 Motor-
prot
0.5 .. 180.0 sec; ∞ 10.0 sec Startup Time for warm
motor
4106 TEMP.COLD
MOTOR
48/66 Motor-
prot
0 .. 80 %; ∞ 25 % Temperature limit for cold
motor
4201 FCT 49 49 Th.Overload OFF
ON
Alarm Only
OFF 49 Thermal overload
protection
4202 49 K-FACTOR 49 Th.Overload 0.10 .. 4.00 1.10 49 K-Factor
4203 TIME CONSTANT 49 Th.Overload 1.0 .. 999.9 min 100.0 min Time Constant
4204 49 Θ ALARM 49 Th.Overload 50 .. 100 % 90 % 49 Thermal Alarm Stage
4205 I ALARM 49 Th.Overload 1A 0.10 .. 4.00 A 1.00 A Current Overload Alarm
Setpoint
5A 0.50 .. 20.00 A 5.00 A
4207A Kτ-FACTOR 49 Th.Overload 1.0 .. 10.0 1.0 Kt-FACTOR when motor
stops
4208A T EMERGENCY 49 Th.Overload 10 .. 15000 sec 100 sec Emergency time
4209 49 TEMP. RISE I 49 Th.Overload 40 .. 200 °C 100 °C 49 Temperature rise at
rated sec. curr.
4210 49 TEMP. RISE I 49 Th.Overload 104 .. 392 °F 212 °F 49 Temperature rise at
rated sec. curr.
4211 TEMPSENSOR RTD 49 Th.Overload 1 .. 6 1 Temperature sensor
connected to RTD
4212 TEMPSENSOR RTD 49 Th.Overload 1 .. 12 1 Temperature sensor
connected to RTD
4301 FCT 66 48/66 Motor-
prot
OFF
ON
OFF 66 Startup Counter for
Motors
4302 IStart/IMOTnom 48/66 Motor-
prot
1.10 .. 10.00 4.90 I Start / I Motor nominal
4303 T START MAX 48/66 Motor-
prot
1 .. 320 sec 10 sec Maximum Permissible
Starting Time
4304 T Equal 48/66 Motor-
prot
0.0 .. 320.0 min 1.0 min Temperature Equalizaton
Time
4305 I MOTOR NOMINAL 48/66 Motor-
prot
1A 0.20 .. 1.20 A 1.00 A Rated Motor Current
5A 1.00 .. 6.00 A 5.00 A
Functions, Settings, Information
F.2 Settings
632 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016