Addr. Parameter Function C Setting Options Default Setting Comments
4306 MAX.WARM
STARTS
48/66 Motor-
prot
1 .. 4 2 Maximum Number of
Warm Starts
4307 #COLD-#WARM 48/66 Motor-
prot
1 .. 2 1 Number of Cold Starts -
Warm Starts
4308 Kτ at STOP 48/66 Motor-
prot
0.2 .. 100.0 5.0 Extension of Time
Constant at Stop
4309 Kτ at RUNNING 48/66 Motor-
prot
0.2 .. 100.0 2.0 Extension of Time
Constant at Running
4310 T MIN. INHIBIT 48/66 Motor-
prot
0.2 .. 120.0 min 6.0 min Minimum Restart Inhibit
Time
4311 ROTOR OVERLOAD 48/66 Motor-
prot
ON
OFF
Alarm Only
ON Rotor Overload Protection
4401 Load Jam Prot. 48/66 Motor-
prot
OFF
ON
Alarm Only
OFF Load Jam Protection
4402 Load Jam I> 48/66 Motor-
prot
1A 0.50 .. 12.00 A 2.00 A Load Jam Tripping
Threshold
5A 2.50 .. 60.00 A 10.00 A
4403 TRIP DELAY 48/66 Motor-
prot
0.00 .. 600.00 sec 1.00 sec Load Jam Trip Delay
4404 I Alarm 48/66 Motor-
prot
1A 0.50 .. 12.00 A 1.80 A Load Jam Alarm
Threshold
5A 2.50 .. 60.00 A 9.00 A
4405 ALARM DELAY 48/66 Motor-
prot
0.00 .. 600.00 sec 1.00 sec Load Jam Alarm Delay
4406 T Start Blk. 48/66 Motor-
prot
0.00 .. 600.00 sec 10.00 sec Load Jam Blocking after
motor start
5001 FCT 59 27/59 O/U Volt. OFF
ON
Alarm Only
OFF 59 Overvoltage Protec-
tion
5002 59-1 PICKUP 27/59 O/U Volt. 40 .. 260 V 110 V 59-1 Pickup
5003 59-1 PICKUP 27/59 O/U Volt. 40 .. 150 V 110 V 59-1 Pickup
5004 59-1 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
∞
0.50 sec 59-1 Time Delay
5005 59-2 PICKUP 27/59 O/U Volt. 40 .. 260 V 120 V 59-2 Pickup
5006 59-2 PICKUP 27/59 O/U Volt. 40 .. 150 V 120 V 59-2 Pickup
5007 59-2 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
∞
0.50 sec 59-2 Time Delay
5015 59-1-V2 PICKUP 27/59 O/U Volt. 2 .. 150 V 30 V 59-1 Pickup Overvoltage
(neg. seq.)
5016 59-2-V2 PICKUP 27/59 O/U Volt. 2 .. 150 V 50 V 59-2 Pickup Overvoltage
(neg. seq.)
5017A 59-1 DOUT RATIO 27/59 O/U Volt. 0.90 .. 0.99 0.95 59-1 Dropout Ratio
5018A 59-2 DOUT RATIO 27/59 O/U Volt. 0.90 .. 0.99 0.95 59-2 Dropout Ratio
5019 59-1 PICKUP V1 27/59 O/U Volt. 40 .. 150 V 110 V 59-1 Pickup V1
5020 59-2 PICKUP V1 27/59 O/U Volt. 40 .. 150 V 120 V 59-2 Pickup V1
5101 FCT 27 27/59 O/U Volt. OFF
ON
Alarm Only
OFF 27 Undervoltage Protec-
tion
5102 27-1 PICKUP 27/59 O/U Volt. 10 .. 210 V 75 V 27-1 Pickup
Functions, Settings, Information