Addr. Parameter Function C Setting Options Default Setting Comments
5103 27-1 PICKUP 27/59 O/U Volt. 10 .. 120 V 75 V 27-1 Pickup
5106 27-1 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
1.50 sec 27-1 Time Delay
5110 27-2 PICKUP 27/59 O/U Volt. 10 .. 210 V 70 V 27-2 Pickup
5111 27-2 PICKUP 27/59 O/U Volt. 10 .. 120 V 70 V 27-2 Pickup
5112 27-2 DELAY 27/59 O/U Volt. 0.00 .. 100.00 sec;
0.50 sec 27-2 Time Delay
5113A 27-1 DOUT RATIO 27/59 O/U Volt. 1.01 .. 3.00 1.20 27-1 Dropout Ratio
5114A 27-2 DOUT RATIO 27/59 O/U Volt. 1.01 .. 3.00 1.20 27-2 Dropout Ratio
5120A CURRENT SUPERV. 27/59 O/U Volt. OFF
ON
ON Current Supervision
5201 VT BROKEN WIRE Meas-
urem.Superv
ON
OFF
OFF VT broken wire supervi-
sion
5202 Σ V> Meas-
urem.Superv
1.0 .. 100.0 V 8.0 V Threshold voltage sum
5203 Vph-ph max< Meas-
urem.Superv
1.0 .. 100.0 V 16.0 V Maximum phase to phase
voltage
5204 Vph-ph min< Meas-
urem.Superv
1.0 .. 100.0 V 16.0 V Minimum phase to phase
voltage
5205 Vph-ph max-min> Meas-
urem.Superv
10.0 .. 200.0 V 16.0 V Symmetry phase to phase
voltages
5206 I min> Meas-
urem.Superv
1A 0.04 .. 1.00 A 0.04 A Minimum line current
5A 0.20 .. 5.00 A 0.20 A
5208 T DELAY ALARM Meas-
urem.Superv
0.00 .. 32.00 sec 1.25 sec Alarm delay time
5301 FUSE FAIL MON. Meas-
urem.Superv
OFF
Solid grounded
Coil.gnd./isol.
OFF Fuse Fail Monitor
5302 FUSE FAIL 3Vo Meas-
urem.Superv
10 .. 100 V 30 V Zero Sequence Voltage
5303 FUSE FAIL RESID Meas-
urem.Superv
1A 0.10 .. 1.00 A 0.10 A Residual Current
5A 0.50 .. 5.00 A 0.50 A
5308A FFM Idiff (3ph) Meas-
urem.Superv
1A 0.05 .. 1.00 A 0.10 A Differential Current
Threshold (3phase)
5A 0.25 .. 5.00 A 0.50 A
5310 BLOCK PROT. Meas-
urem.Superv
NO
YES
YES Block protection by FFM
5401 FCT 81 O/U 81 O/U Freq. OFF
ON
OFF 81 Over/Under Frequency
Protection
5402 Vmin 81 O/U Freq. 10 .. 150 V 65 V Minimum required
voltage for operation
5403 81-1 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 49.50 Hz 81-1 Pickup
5404 81-1 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 59.50 Hz 81-1 Pickup
5405 81-1 DELAY 81 O/U Freq. 0.00 .. 100.00 sec;
60.00 sec 81-1 Time Delay
5406 81-2 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 49.00 Hz 81-2 Pickup
5407 81-2 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 59.00 Hz 81-2 Pickup
5408 81-2 DELAY 81 O/U Freq. 0.00 .. 100.00 sec;
30.00 sec 81-2 Time Delay
5409 81-3 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 47.50 Hz 81-3 Pickup
Functions, Settings, Information
F.2 Settings
634 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016