Addr. Parameter Function C Setting Options Default Setting Comments
5410 81-3 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 57.50 Hz 81-3 Pickup
5411 81-3 DELAY 81 O/U Freq. 0.00 .. 100.00 sec;
3.00 sec 81-3 Time delay
5412 81-4 PICKUP 81 O/U Freq. 40.00 .. 60.00 Hz 51.00 Hz 81-4 Pickup
5413 81-4 PICKUP 81 O/U Freq. 50.00 .. 70.00 Hz 61.00 Hz 81-4 Pickup
5414 81-4 DELAY 81 O/U Freq. 0.00 .. 100.00 sec;
30.00 sec 81-4 Time delay
5415A DO differential 81 O/U Freq. 0.02 .. 1.00 Hz 0.02 Hz Dropout differential
5421 FCT 81-1 O/U 81 O/U Freq. OFF
ON f>
ON f<
OFF 81-1 Over/Under
Frequency Protection
5422 FCT 81-2 O/U 81 O/U Freq. OFF
ON f>
ON f<
OFF 81-2 Over/Under
Frequency Protection
5423 FCT 81-3 O/U 81 O/U Freq. OFF
ON f>
ON f<
OFF 81-3 Over/Under
Frequency Protection
5424 FCT 81-4 O/U 81 O/U Freq. OFF
ON f>
ON f<
OFF 81-4 Over/Under
Frequency Protection
5501 27/Q-Protection 27/Q OFF
ON
OFF 27 / Q dir. con. Protection
5502 I-Release 27/Q 1A 0.02 .. 0.20 A; 0 0.10 A Current-Rel. for Trip and
Reclose
5A 0.10 .. 1.00 A; 0 0.50 A
5503 Inrush blk 27/Q NO
YES
NO blocking with inrush
5511 Q> Pickup 27/Q 1A 1.70 ..
10000.00 VAR
8.70 VAR Reactive power threshold
for pickup
5A 8.50 ..
50000.00 VAR
43.50 VAR
5512 U< Pickup 27/Q 10.00 .. 210.00 V 85.00 V Undervoltage threshold
for pickup
5513 Delay Gen. CB 27/Q 0.00 .. 60.00 sec 0.50 sec Trip time delay generator
CB
5514 Delay Grid CB 27/Q 0.00 .. 60.00 sec 1.50 sec Trip time delay grid CB
5521 Recl. release 27/Q OFF
ON
OFF Reclosure release
5522 U> Reclose 27/Q 10.00 .. 210.00 V 95.00 V Voltage threshold for
reclosure rel.
5523 T Reclose 27/Q 0.00 .. 3600.00 sec 0.00 sec Reclosure Delay Time
5524 Pos. f-diff 27/Q 0.01 .. 5.00 Hz 0.05 Hz Pos. f-diff threshold for
reclosure rel.
5525 Neg. f-diff 27/Q -5.00 .. -0.01 Hz -2.50 Hz Neg. f-diff threshold for
reclosure rel.
5526A Incl. 27/Q Trip 27/Q NO
YES
NO Include 27/Q Trip for
reclosure rel.
6001 S1: RE/RL P.System Data
2
-0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor RE/RL