Addr. Parameter Function C Setting Options Default Setting Comments
6002 S1: XE/XL P.System Data
2
-0.33 .. 7.00 1.00 S1: Zero seq. compen-
sating factor XE/XL
6003 S1: x' P.System Data
2
1A 0.0050 ..
15.0000 Ω/mi
0.2420 Ω/mi S1: feeder reactance per
mile: x'
5A 0.0010 ..
3.0000 Ω/mi
0.0484 Ω/mi
6004 S1: x' P.System Data
2
1A 0.0050 ..
9.5000 Ω/km
0.1500 Ω/km S1: feeder reactance per
km: x'
5A 0.0010 ..
1.9000 Ω/km
0.0300 Ω/km
6005 S1: Line angle P.System Data
2
10 .. 89 ° 85 ° S1: Line angle
6006 S1: line length P.System Data
2
0.1 .. 650.0 Miles 62.1 Miles S1: Line length in miles
6007 S1: Line length P.System Data
2
0.1 .. 1000.0 km 100.0 km S1: Line length in kilo-
meter
6011 S2: RE/RL P.System Data
2
-0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor RE/RL
6012 S2: XE/XL P.System Data
2
-0.33 .. 7.00 1.00 S2: Zero seq. compen-
sating factor XE/XL
6013 S2: x' P.System Data
2
1A 0.0050 ..
15.0000 Ω/mi
0.2420 Ω/mi S2: feeder reactance per
mile: x'
5A 0.0010 ..
3.0000 Ω/mi
0.0484 Ω/mi
6014 S2: x' P.System Data
2
1A 0.0050 ..
9.5000 Ω/km
0.1500 Ω/km S2: feeder reactance per
km: x'
5A 0.0010 ..
1.9000 Ω/km
0.0300 Ω/km
6015 S2: Line angle P.System Data
2
10 .. 89 ° 85 ° S2: Line angle
6016 S2: line length P.System Data
2
0.1 .. 650.0 Miles 62.1 Miles S2: line length in miles
6017 S2: Line length P.System Data
2
0.1 .. 1000.0 km 100.0 km S2: Line length in kilo-
meter
6021 S3: RE/RL P.System Data
2
-0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor RE/RL
6022 S3: XE/XL P.System Data
2
-0.33 .. 7.00 1.00 S3: Zero seq. compen-
sating factor XE/XL
6023 S3: x' P.System Data
2
1A 0.0050 ..
15.0000 Ω/mi
0.2420 Ω/mi S3: feeder reactance per
mile: x'
5A 0.0010 ..
3.0000 Ω/mi
0.0484 Ω/mi
6024 S3: x' P.System Data
2
1A 0.0050 ..
9.5000 Ω/km
0.1500 Ω/km S3: feeder reactance per
km: x'
5A 0.0010 ..
1.9000 Ω/km
0.0300 Ω/km
6025 S3: Line angle P.System Data
2
10 .. 89 ° 85 ° S3: Line angle
6026 S3: line length P.System Data
2
0.1 .. 650.0 Miles 62.1 Miles S3: line length in miles
6027 S3: Line length P.System Data
2
0.1 .. 1000.0 km 100.0 km S3: Line length in kilo-
meter
Functions, Settings, Information
F.2 Settings
636 SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016