EasyManua.ls Logo

Siemens SIPROTEC 4 - Page 701

Siemens SIPROTEC 4
734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Description Function Typ
e of
Info
rma
tion
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
information number
Data Unit
General Interrogation
6812 48 Motor Startup Time
Superv. BLOCKED (48
BLOCKED)
48/66
Motorprot
OUT On
Of
f
On
Off
* LED BO 16
9
52 1 Yes
6813 48 Motor Startup Time
Supervision ACTIVE (48
ACTIVE)
48/66
Motorprot
OUT On
Of
f
* * LED BO 16
9
53 1 Yes
6821 48 Motor Startup Time
Supervision TRIP (48 TRIP)
48/66
Motorprot
OUT * On m LED BO 16
9
54 2 Yes
6822 48/14 Mot.St.Time Sup.
Rotor locked (48 Rotor
locked)
48/66
Motorprot
OUT * On * LED BO 16
9
55 2 Yes
6823 48 Motor Startup Time
Superv. picked up (48
pickup)
48/66
Motorprot
OUT On
Of
f
* * LED BO 16
9
56 1 Yes
6851 >BLOCK 74TC (>BLOCK
74TC)
74TC Trip-
Circ.
SP * * * LED BI BO
6852 >74TC Trip circuit superv.:
trip relay (>74TC trip rel.)
74TC Trip-
Circ.
SP On
Of
f
* * LED BI BO 17
0
51 1 Yes
6853 >74TC Trip circuit superv.:
brk relay (>74TC brk rel.)
74TC Trip-
Circ.
SP On
Of
f
* * LED BI BO 17
0
52 1 Yes
6861 74TC Trip circuit supervi-
sion OFF (74TC OFF)
74TC Trip-
Circ.
OUT On
Of
f
* * LED BO 17
0
53 1 Yes
6862 74TC Trip circuit supervi-
sion is BLOCKED (74TC
BLOCKED)
74TC Trip-
Circ.
OUT On
Of
f
On
Off
* LED BO 15
3
16 1 Yes
6863 74TC Trip circuit supervi-
sion is ACTIVE (74TC
ACTIVE)
74TC Trip-
Circ.
OUT On
Of
f
* * LED BO 15
3
17 1 Yes
6864 74TC blocked. Bin. input
is not set (74TC ProgFail)
74TC Trip-
Circ.
OUT On
Of
f
* * LED BO 17
0
54 1 Yes
6865 74TC Failure Trip Circuit
(74TC Trip cir.)
74TC Trip-
Circ.
OUT On
Of
f
* * LED BO 17
0
55 1 Yes
6903 >block interm. E/F prot.
(>IEF block)
Intermit. EF SP * * * LED BI BO 15
2
1 1 Yes
6921 Interm. E/F prot. is
switched off (IEF OFF)
Intermit. EF OUT On
Of
f
* * LED BO 15
2
10 1 Yes
Functions, Settings, Information
F.3 Information List
SIPROTEC 4, 7SJ62/64, Manual 701
C53000-G1140-C207-8, Edition 08.2016

Table of Contents

Other manuals for Siemens SIPROTEC 4

Related product manuals