Configuration
5-12 7SA6 Manual
C53000-G1176-C133-1
described in general in Chapter 4. Details regarding the settings for various functions
are found in Chapter 6.
The settings group to be processed may be selected via the menu item 9LHZ →
6HWWLQJ*URXS.
Information The column header ,QIRUPDWLRQ contains the function number, the LCD text
(display text), an explanation (long text), and the information type. The following
abbreviations are used for the information types:
• Annunciations:
− SP Single Point Indication (binary input, e.g. LED reset, refer also to
subsection 5.2.1)
− DP Double Point Indication (binary input, refer also to subsection 5.2.1)
− OUT Output Indication (protection output signals e.g. pickup, trip ...)
− IntSP Internal Single Point Indication,
− IntDP Internal Double Point Indication.
− TxTap Transformer Tap Indication
• Control Commands for switching devices (refer to subsection 5.2.3):
− C_S Single Command with Single Output without Feedback,
− CF_S Single Command with Single Output with Feedback,
− C_SN Single Command with Single Output Negated without Feedback,
− C_D2 Double Command (2 relays) with Single Outputs without Feedback,
− CF_D2 Double Command (2 relays) with Single Outputs with Feedback,
− C_D12 Double Command with Single Trip Outputs and Double Close Outputs
without Feedback,
− CF_D12 Double Command with Single Trip Outputs and Double Close Outputs
with Feedback,
− C_D3 Double Command (3 relays) with Single Outputs and Common Output
without Feedback,
− CF_D3 Double Command (3 relays) with Single Outputs and Common Output
with Feedback,
− C_D4 Double Command (4 relays) with Double Outputs without Feedback,
− CF_D4 Double Command (4 relays) with Double Outputs with Feedback,
− C_D2N Double Command (2 relays) with Single Outputs Negated
without Feedback,
− CF_D2N Double Command (2 relays) with Single Outputs Negated with
Feedback.
• Measured Values:
− MV Measured Value,
− MVU Measured Value, User Defined,
− MVT Measured Value with Time,
− LV Limit Value,
− LVU Limit Value, User Defined.
• Metered Values:
− MVMV Metered Value of Measured Value,
− PMV Pulse Measured Value.
The information contains various properties depending on the information type, which
are partially fixed and may be partially influenced.