Functions
6-296 7SA6 Manual
C53000-G1176-C133-1
Status information commands for setting / deactivating the “information status” for
the information value of an object:
Controlling activation of binary input status
Blocking binary outputs
6.22.2 Steps in the Command Sequence
Safety mechanisms in the command sequence ensure that a command can only be
released after a thorough check of preset criteria has been successfully concluded.
Additionally, user-defined interlocking conditions can be configured separately for
each device. The actual execution of the command is also monitored afterwards. The
entire sequence of a command is described briefly in the following:
Check Sequence Command entry (e.g. using the keypad on the local user interface of the device)
Check password access rights
Check switching mode (interlocking activated/deactivated) selection of
deactivated interlocking status
User configurable interlocking checks that can be selected for each command
Switching authority (local, remote)
Switching direction control (target state = present state)
Zone controlled/bay interlocking (logic using CFC)
System interlocking (centrally via SICAM)
Double operation (interlocking against parallel switching operation)
Protection blocking (blocking of switching operations by protective functions)
Fixed commands
Timeout monitoring (time between command initiation and the beginning of the
execution can be controlled).
Configuration in process (if setting modification is in process, commands are
rejected or delayed)
Equipment not present at output (if controllable equipment is not assigned to a
binary output, then the command is denied)
Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is denied)
Component hardware malfunction
Command in progress (only one command can be processed at a time for each
circuit breaker or switch)
1- out of -n-check (for schemes with multiple assignments, such as common
ground, it is checked whether a command has already been initiated for the
affected output relay).

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals