Initial Inspections
3-137SA6 Manual
C53000-G1176-C133-1
3.4 Storage
If the device is to be stored, note:
SIPROTEC
®
4 devices and associated assemblies should be stored in dry and clean
rooms, with a maximum temperature range of –25° C to +55° C (–12° F to 131° F).
See Sub-section 10.1.7 under Technical Data. To avoid premature aging of the
electrolyte capacitors in the power supply, a temperature range of +10° C to +35° C
(50° F to 95° F), is recommended for storage.
The relative humidity must not lead to condensation or ice buildup.
After extended storage, the power supply of the device should be energized,
approximately every two years, for one or two days to regenerate the electrolytic
capacitors in the power supply. This procedure should also be done prior to the device
being put in service. Under extreme climatic conditions (tropics), pre-warming is
achieved at the same time, and condensation is prevented.
After long storage, power should not be applied until the device has been in the
operating area for a minimum of two hours. This time period allows the device to attain
temperature equilibrium, and prevents dampness and condensation from occurring.
To save the energy of the buffer battery inside the device, the battery is switched off
automatically without auxiliary supply voltage after a time period of 1 to 2 days.