EasyManuals Logo

Siemens siprotec 7SA6 User Manual

Siemens siprotec 7SA6
792 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #393 background imageLoading...
Page #393 background image
Functions
6-2117SA6 Manual
C53000-G1176-C133-1
6.14.1.2 Undervoltage Protection
Undervoltage
Phase–Earth
Figure 6-108 depicts the logic diagram of the phase voltage stages. The fundamental
frequency is numerically filtered from each of the three measuring voltages so that
harmonics or transient voltage peaks are largely harmless. Two threshold stages
8SKH and 8SKHare compared with the voltages. If phase voltage falls below
a threshold it is indicated phase-segregated. Furthermore, a general pick-up indication
8SKH3LFNXS” or “8SKH3LFNXS” is given. The drop-off to pick-up ratio is
1.05.
Each stage starts a time delay common to all phases. Expiry of the respective time
delay
78SKHor 78SKH is signalled and results in the trip command “8SKH
75,3”.
Depending on the configuration of the substations the voltage transformers are
located on the busbar side or on the outgoing feeder side. This results in a different
behaviour of the undervoltage protection when the line is deenergized. While the
voltage remains present or reappears at the busbar side after a trip command and
opening of the circuit breaker, it is switched on at the outgoing side. For the
undervoltage protection this results in a pick-up state being present if the voltage
transformers are on the outgoing side. If this pick-up must be reset, the current can be
used as an additional criterion (current supervision &855683) to achieve this result.
Undervoltage will then only be detected if, together with the undervoltage condition,
the minimum current 3ROH2SHQ&XUUHQW (address ) of the corresponding phase
is also exceeded. This condition is communicated by the central function control of the
device.
The undervoltage protection phase–earth can be blocked via the binary input
!8SKH%/.”. The stages of the undervoltage protection are then automatically
blocked if a voltage failure is detected (“Fuse–Failure–Monitor”, also see Section
6.19.1.3) or if the trip of the mcb of the voltage transformers is indicated (internal
blocking) via the binary input !)$,/)HHGHU97”.
Also during a single-pole automatic reclose dead time (using the internal
autoreclosure function) the stages of the undervoltage protection are automatically
blocked in the pole open state. If necessary, the current criterion will be considered,
so that they do not respond to the undervoltage of the disconnected phase when
voltage transformers are located on the outgoing side.

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals