Functions
6-2217SA6 Manual
C53000-G1176-C133-1
6.15 Fault Location
Measurement of the distance to fault in the event of a short circuit is an important
supplement to the protection functions. The availability of the line for transmission of
energy in the system can be increased by a more rapid determination of the fault
location and repair of any resultant damage.
6.15.1 Method of Operation
Starting Conditions The fault location function in the distance protection 7SA6 is a function which is
independent of the distance measurement. It has a separate measured value memory
and dedicated filter algorithms. The short-circuit protection merely has to provide a
start command to allow the selection of the valid measuring loop and the best suited
time interval for the storage of the measured signals.
The fault location function can be triggered by the trip command of the short-circuit
protection, or also by each fault detection. In the latter case, a fault location calculation
is also possible if a different protection device clears the fault. In the case of a fault
outside of the protected feeder, the fault location output cannot always be correct,
because the measured values may be distorted by for instance an intermediate infeed.
Determination of
the Fault Location
The measured value pairs of fault currents and fault voltages (in intervals of
1
/
20
AC
cycle) are stored in a circular buffer and frozen shortly after the trip command is issued
before any distortion of the measured values occurs due to the opening of the circuit
breaker even with very fast circuit breakers. Filtering of the measured values and the
number of impedance calculations are automatically adapted to the number of
stabilized measured value pairs in the determined data window. If a sufficient data
window with stabilized values could not be determined, the alarm
)OW/RFLQYDOLG” is issued.
The evaluation of the measured values in the short-circuit loops is carried out after the
short-circuit has been cleared. Short-circuit loops are those, which caused the trip. In
the event of tripping by the earth fault protection, the three phase–earth loops are
evaluated.
With the memorized and filtered measured values, at least three pairs of results for R
and X are determined according to the line equation. With the pairs of results, the
average values and standard deviations are calculated. After elimination of “deviants”
which are recognized by their large deviation from the standard deviation, a new
average is calculated. This average for X is the fault reactance which is proportional
to the distance to fault. If several loops were evaluated, the loop with the smallest
reactance is valid. In this manner, the fault on the protected feeder is in any event
determined during multiple faults or in the event of tripping by only the earth fault
protection.
Output of the Fault
Location
The fault location function issues the following results:
the short-circuit loop which was used to determine the fault reactance,
the reactance X per phase in primary and secondary,
the resistance R per phase in primary and secondary,
the distance to fault d in kilometres or miles of the line proportional to the reactance,
converted based on the set line reactance per unit line length,

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals