Appendix
A-477SA6 Manual
C53000-G1176-C133-1
A.5 Protocol Dependent Functions
Protocol → IEC 60870–5–103
Profibus FMS Additional
Service
Interface
(optional)
Function ↓
Operational Measured
Values
Yes
Yes Yes
Metering Values
Yes Yes
Yes
Fault Recording Yes Yes Yes
Protective Setting from
Remote
No. Only via Additional
Service Interface
Yes Yes
User-defined Alarms
and Switching Objects
Yes Yes Yes
Time Sychronism Via Protocol;
DCF77/IRIG B;
Interface;
Binary Input
Via Protocol;
DCF77/IRIG B;
Interface;
Binary Input
–
Alarms with Time
Stamp
Yes Yes Yes
Commissioning Tools:
• Alarm and Measured
Value Transmission
Blocking
Yes Yes Yes
• Generate Test
Alarms
Yes Yes Yes
Physical Mode Asynchronous Asynchronous
–
Transmission Mode Cyclic/Event Cyclic/Event
–
Baudrate 4800 to 38400 Up to 1.5 MBaud 2400 to 115200
Type RS232
RS485
Optical Fibres
RS485
Optical Fibres
• Single-ended
Ring
• Double-ended
Ring
RS232
RS485
Optical Fibres