Functions
6-657SA6 Manual
C53000-G1176-C133-1
1341 Op. mode Z5 Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode Z5
1342 R(Z5) Ø-Ø 0.05..250.00 Ohm 12.00 Ohm R(Z5), Resistance for ph-ph-
faults
1343 X(Z5)+ 0.05..250.00 Ohm 12.00 Ohm X(Z5)+, Reactance for Forward
direction
1344 RE(Z5) Ø-E 0.05..250.00 Ohm 12.00 Ohm RE(Z5), Resistance for ph-e
faults
1345 T5 DELAY 0.00..30.00 sec; 0.90 sec T5 delay
1346 X(Z5)- 0.05..250.00 Ohm 4.00 Ohm X(Z5)-, Reactance for Reverse
direction
Addr. Setting Title Setting Options Default Setting Comments