Functions
6-2037SA6 Manual
C53000-G1176-C133-1
FKHFN, no checks are performed before manual closing. The following parameters are
then irrelevant.
Address 2SPRGHZLWK0& determines whether closing under asynchronous
system conditions is allowed. Set this parameter to ZLWK7&%FORVH, if
asynchronous closing shall be allowed; the relay will then consider the circuit breaker
closing time before determining the correct instant for the close command. Remember
that closing under asynchronous system conditions is allowed only if the circuit
breaker closing time is set correctly (see above under “Preconditions”)! If you wish to
only permit manual closing under synchronous system conditions, set this address to
ZR7&%FORVH.
The permissible magnitude difference of the voltages is set under address  0&
PD[9ROW'LII. Setting is in volts secondary. When operating the device from a
personal computer using DIGSI
®
4, setting may be in secondary or primary values.
Depending on the connection of the bus-bar voltage (phase–phase or phase–earth)
the phase–phase or the phase–earth voltage is decisive.
The permissible frequency difference between the voltages is set under address 
0&PD[)UHT'LII, the permissible phase angle difference under address 0&
PD[$QJOH'LII.
The release conditions for manual closing are set under addresses $ to :
$ 0&6<1&+5 = synchronism check: the bus-bar (Ubus) and the
feeder (Uline) must both be live (/LYH9ROW
7KU, address ); the conditions for
synchronism 0&PD[9ROW'LII (address ),
0&PD[)UHT'LII (address ), and 0&
PD[$QJOH'LII (address ) are checked
before manual closure;
 0&8V\Q!8OLQH dead-line check: the bus-bar (Ubus) must be live
(/LYH9ROW7KU, refer to address ), the
feeder (Uline) must be dead ('HDG9ROW7KU,
refer to address );
 0&8V\Q8OLQH! dead-bus check: the bus-bar (Ubus) must be dead
('HDG9ROW7KU, refer to address ), the
feeder (Uline) must be live (/LYH9ROW7KU,
refer to address );
 0&8V\Q8OLQH = dead-bus and dead-line check: the bus-bar (Ubus)
and the feeder (Uline) must both be dead ('HDG
9ROW7KU, refer to address );
 0&25,'( = manual closing is released without any check.
The five possible release conditions are independent of each other and can be
combined.

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals