Appendix
B-9
7SA6 Manual
C53000-G1176-C133-1
1602 DELAY FORW. PU Distance protec-
tion, general set-
tings
0.00..30.00 sec; 1.20 sec Trip delay for Forward-PICKUP
1603 DELAY NON-DIR Distance protec-
tion, general set-
tings
0.00..30.00 sec; 1.20 sec Trip delay for Reverse/Non-direc.
PICKUP
1610 Iph>> Distance protec-
tion, general set-
tings
0.25..10.00 A 1.80 A Iph>> Pickup (overcurrent)
1611 Iph> Distance protec-
tion, general set-
tings
0.10..4.00 A 0.20 A Iph> Pickup (minimum current)
1612 Uph-e (I>>) Distance protec-
tion, general set-
tings
20..70 V 48 V Undervoltage (ph-e) at Iph>>
1613 Uph-e (I>) Distance protec-
tion, general set-
tings
20..70 V 48 V Undervoltage (ph-e) at Iph>
1614 Uph-ph (I>>) Distance protec-
tion, general set-
tings
40..130 V 80 V Undervoltage (ph-ph) at Iph>>
1615 Uph-ph (I>) Distance protec-
tion, general set-
tings
40..130 V 80 V Undervoltage (ph-ph) at Iph>
1616 Iphi> Distance protec-
tion, general set-
tings
0.10..8.00 A 0.50 A Iphi> Pickup (minimum current at phi>)
1617 Uph-e (Iphi>) Distance protec-
tion, general set-
tings
20..70 V 48 V Undervoltage (ph-e) at Iphi>
1618 Uph-ph (Iphi>) Distance protec-
tion, general set-
tings
40..130 V 80 V Undervoltage (ph-ph) at Iphi>
1619A EFFECT ϕ Distance protec-
tion, general set-
tings
forward and reverse
Forward
forward and reverse Effective direction of phi-pickup
1620 ϕ > Distance protec-
tion, general set-
tings
30..60 ° 50 ° PHI> pickup (lower setpoint)
1621 ϕ < Distance protec-
tion, general set-
tings
90..120 ° 110 ° PHI< pickup (upper setpoint)
1630A 1ph FAULTS Distance protec-
tion, general set-
tings
phase-earth
phase to phase only
phase-earth 1ph-pickup loop selection (PU w/o
earth)
2002 P/S Op. mode Power Swing all zones blocked
Z1/Z1B blocked
Z2 to Z5 blocked
Z1,Z1B,Z2 blocked
all zones blocked Power Swing Operating mode
2006 PowerSwing trip Power Swing NO
YES
NO Power swing trip
2101 FCT Telep. Dis. Teleprotection for
Distance prot.
ON
OFF
ON Teleprotection for Distance prot. is
2102 Type of Line Teleprotection for
Distance prot.
Two Terminals
Three Terminals
Two Terminals Type of Line
2103A Send Prolong. Teleprotection for
Distance prot.
0.00..30.00 sec 0.05 sec Time for send signal prolongation
2107A Delay for alarm Teleprotection for
Distance prot.
0.00..30.00 sec 10.00 sec Unblocking: Time Delay for Alarm
2108 Release Delay Teleprotection for
Distance prot.
0.000..30.000 sec 0.000 sec Time Delay for release after pickup
Addr. Setting Title Function Setting Options Default Setting Comments