562 CB CLOSE command for manual
closing (Man.Close Cmd)
Power System
Data 2
OUT * * LED BO 150 212 1
563 CB alarm suppressed (CB Alarm
Supp)
Power System
Data 2
OUT * * * LED BO
601 I L1 (IL1 =) Measurement MV 128
134
148
124
3
9
602 I L2 (IL2 =) Measurement MV 128
134
148
124
3
9
603 I L3 (IL3 =) Measurement MV 128
134
148
124
3
9
610 3I0 (zero sequence) (3I0 =) Measurement MV 134 124 9
611 3I0sen (sensitive zero sequence)
(3I0sen=)
Measurement MV
612 IY (star point of transformer) (IY =) Measurement MV
613 3I0par (parallel line neutral)
(3I0par=)
Measurement MV
619 I1 (positive sequence) (I1 =) Measurement MV
620 I2 (negative sequence) (I2 =) Measurement MV
621 U L1-E (UL1E=) Measurement MV 128
134
148
124
3
9
622 U L2-E (UL2E=) Measurement MV 128
134
148
124
3
9
623 U L3-E (UL3E=) Measurement MV 128
134
148
124
3
9
624 U L12 (UL12=) Measurement MV 134 124 9
625 U L23 (UL23=) Measurement MV 134 124 9
626 U L31 (UL31=) Measurement MV 134 124 9
631 3U0 (zero sequence) (3U0 =) Measurement MV
632 Usync (synchronism) (Usync =) Measurement MV
633 Ux (separate VT) (Ux =) Measurement MV
634 U1 (positive sequence) (U1 =) Measurement MV
635 U2 (negative sequence) (U2 =) Measurement MV
636 U-diff (line-bus) (Udiff =) Measurement MV
637 U-line (Uline =) Measurement MV
641 P (active power) (P =) Measurement MV 128
134
148
124
3
9
642 Q (reactive power) (Q =) Measurement MV 128
134
148
124
3
9
643 Power Factor (PF =) Measurement MV 134 124 9
644 Frequency (Freq=) Measurement MV 128
134
148
124
3
9
645 S (apparent power) (S =) Measurement MV
646 Frequency (busbar) (F-bus =) Measurement MV
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation