B-32
1220 Reactive 3I0sen (sensitive Ie) =
(3I0senR=)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON
OFF
1251 >Switch on sensitive E/F detection
(>SensEF on)
Sensitive Earth
Flt.(comp/ isol.
starp.)
SP * * LED BI BO
1252 >Switch off sensitive E/F detection
(>SensEF off)
Sensitive Earth
Flt.(comp/ isol.
starp.)
SP * * LED BI BO
1253 >Block sensitive E/F detection
(>SensEF block)
Sensitive Earth
Flt.(comp/ isol.
starp.)
SP * * LED BI BO
1260 Sensitve E/F detection ON/OFF via
BI (SensEF on/offBI)
Sensitive Earth
Flt.(comp/ isol.
starp.)
IntSP ON
OFF
* LED BO
1261 Sensitve E/F detection is switched
OFF (SensEF OFF)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT ON
OFF
* LED BO 151 161 1 GI
1262 Sensitve E/F detection is BLOCKED
(SensEF BLOCK)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT ON
OFF
ON
OFF
LED BO 151 162 1 GI
1263 Sensitve E/F detection is ACTIVE
(SensEF ACTIVE)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT ON
OFF
* LED BO 151 163 1 GI
1271 Sensitve E/F detection picked up
(SensEF Pickup)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT ON
OFF
ON
OFF
ON M LED BO
1272 Sensitve E/F detection Phase L1
(SensEF Phase L1)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 128 48 2 GI
1273 Sensitve E/F detection Phase L2
(SensEF Phase L2)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 128 49 2 GI
1274 Sensitve E/F detection Phase L3
(SensEF Phase L3)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 128 50 2 GI
1276 Sensitve E/F detection Forward
(SensEF Forward)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 128 51 2 GI
1277 Sensitve E/F detection Reverse
(SensEF Reverse)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 128 52 2 GI
1278 Sensitve E/F detection Undef. Direc-
tion (SensEF undefDir)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * ON LED BO 151 178 2 GI
1281 Sensitve E/F detection TRIP com-
mand (SensEF TRIP)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * ON ON LED BO 151 181 2 GI
1291 Sensitve E/F detection 3U0> pickup
(SensEF 3U0>)
Sensitive Earth
Flt.(comp/ isol.
starp.)
OUT * * LED BO
1305 >Earth Fault O/C Block 3I0>>> (>EF
BLK 3I0>>>)
Earth fault over-
current
SP ON
OFF
* LED BI BO 166 5 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents