Appendix
B-34
1356 E/F 3I0> PICKED UP (EF 3I0>
Pikkup)
Earth fault over-
current
OUT * ON LED BO
1357 E/F 3I0p PICKED UP (EF 3I0p
Pikkup)
Earth fault over-
current
OUT * ON LED BO
1358 E/F picked up FORWARD (EF for-
ward)
Earth fault over-
current
OUT * ON LED BO 166 58 2
1359 E/F picked up REVERSE (EF
reverse)
Earth fault over-
current
OUT * ON LED BO 166 59 2
1361 E/F General TRIP command (EF
Trip)
Earth fault over-
current
OUT * * LED BO 166 61 2
1366 E/F 3I0>>> TRIP (EF 3I0>>> TRIP) Earth fault over-
current
OUT * ON LED BO 166 66 2
1367 E/F 3I0>> TRIP (EF 3I0>> TRIP) Earth fault over-
current
OUT * ON LED BO 166 67 2
1368 E/F 3I0> TRIP (EF 3I0> TRIP) Earth fault over-
current
OUT * ON LED BO 166 68 2
1369 E/F 3I0p TRIP (EF 3I0p TRIP) Earth fault over-
current
OUT * ON LED BO 166 69 2
1370 E/F Inrush picked up (EF InrushPU) Earth fault over-
current
OUT * ON
OFF
LED BO 166 70 2
1380 E/F Teleprot. ON/OFF via BI (EF
TeleON/offBI)
Teleprotection for
Earth fault over-
curr.
IntSP ON
OFF
* LED BO
1381 E/F Teleprotection is switched OFF
(EF Telep. OFF)
Teleprotection for
Earth fault over-
curr.
OUT ON
OFF
* LED BO 166 81 1 GI
1384 E/F Telep. Carrier SEND signal (EF
Tele SEND)
Teleprotection for
Earth fault over-
curr.
OUT on on LED BO 166 84 2
1386 E/F Telep. Transient Blocking (EF
TeleTransBlk)
Teleprotection for
Earth fault over-
curr.
OUT * ON LED BO 166 86 2
1387 E/F Telep. Unblocking: FAILURE
Channel 1 (EF TeleUB Fail1)
Teleprotection for
Earth fault over-
curr.
OUT ON
OFF
* LED BO 166 87 1 GI
1388 E/F Telep. Unblocking: FAILURE
Channel 2 (EF TeleUB Fail2)
Teleprotection for
Earth fault over-
curr.
OUT ON
OFF
* LED BO 166 88 1 GI
1389 E/F Telep. Blocking: carrier STOP
signal (EF Tele BL STOP)
Teleprotection for
Earth fault over-
curr.
OUT * on LED BO 166 89 2
1390 E/F Tele.Blocking: Send signal with
jump (EF Tele BL Jump)
Teleprotection for
Earth fault over-
curr.
OUT * * LED BO 166 90 2
1401 >BF: Switch on breaker fail protec-
tion (>BF on)
Breaker Failure SP * * LED BI BO
1402 >BF: Switch off breaker fail protec-
tion (>BF off)
Breaker Failure SP * * LED BI BO
1403 >BLOCK Breaker failure (>BLOCK
BkrFail)
Breaker Failure SP ON
OFF
* LED BI BO 166 103 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation