Appendix
B-39
7SA6 Manual
C53000-G1176-C133-1
2894 AR Remote close signal send (AR
Remote Close)
Automatic Reclo-
sure
OUT * ON LED BO 40 129 1
2895 No. of 1st AR-cycle CLOSE com-
mands,1pole (AR #Close1./1p=)
Statistics OUT
2896 No. of 1st AR-cycle CLOSE com-
mands,3pole (AR #Close1./3p=)
Statistics OUT
2897 No. of higher AR-cycle CLOSE com-
mands,1p (AR #Close2./1p=)
Statistics OUT
2898 No. of higher AR-cycle CLOSE com-
mands,3p (AR #Close2./3p=)
Statistics OUT
2901 >Switch on synchro-check function
(>Sync. on)
Synchronism and
Voltage Check
SP * * LED BI BO
2902 >Switch off synchro-check function
(>Sync. off)
Synchronism and
Voltage Check
SP * * LED BI BO
2903 >BLOCK synchro-check function
(>BLOCK Sync.)
Synchronism and
Voltage Check
SP * * LED BI BO
2906 >Start synchro-check (>Sync. Start) Synchronism and
Voltage Check
SP on
off
* LED BI BO
2907 >Sync-Prog. Live bus / live line /
Sync (>Sync. synch)
Synchronism and
Voltage Check
SP * * LED BI BO
2908 >Sync-Prog. Dead bus / live line (>
Usyn< U-line>)
Synchronism and
Voltage Check
SP * * LED BI BO
2909 >Sync-Prog. Live bus / dead line (>
Usyn> U-line<)
Synchronism and
Voltage Check
SP * * LED BI BO
2910 >Sync-Prog. Dead bus / dead line (>
Usyn< U-line<)
Synchronism and
Voltage Check
SP * * LED BI BO
2911 >Sync-Prog. Override ( bypass )
(>Sync. o/ride)
Synchronism and
Voltage Check
SP * * LED BI BO
2930 Synchro-check ON/OFF via BI
(Sync. on/off BI)
Synchronism and
Voltage Check
IntSP ON
OFF
* LED BO
2931 Synchro-check is switched OFF
(Sync. OFF)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 31 1 GI
2932 Synchro-check is BLOCKED (Sync.
BLOCK)
Synchronism and
Voltage Check
OUT ON
OFF
ON
OFF
LED BO 41 32 1 GI
2934 Synchro-check function faulty (Sync.
faulty)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 34 1 GI
2935 Synchro-check supervision time
expired (Sync.Tsup.Exp)
Synchronism and
Voltage Check
OUT ON ON LED BO 41 35 1
2941 Synchronization is running (Sync.
running)
Synchronism and
Voltage Check
OUT ON
OFF
ON LED BO 41 41 1 GI
2942 Synchro-check override/bypass
(Sync.Override)
Synchronism and
Voltage Check
OUT ON
OFF
ON LED BO 41 42 1 GI
2943 Synchronism detected (Synchro-
nism)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 43 1 GI
2944 Sync. dead bus / live line detected
(Usyn< U-line>)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 44 1 GI
2945 Sync. live bus / dead line detected
(Usyn> U-line<)
Synchronism and
Voltage Check
OUT ON
OFF
* LED BO 41 45 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation