Cabinet Modules
5.1 Line Connection Modules
Cabinet Modules NEMA
136 Manual, 04/2014, A5E03586450A
Table 5- 4 Factory setting of the overcurrent release on Line Connection Modules for Smart Line Modules
Order number
Line Connection
Module
Order number
Smart Line Module
Input current
Line Module
Short-time de-
layed short-
circuit release
(S)
Delay time short-
circuit release
(t
sd
)
6SL3700-0LE42-0BU3 6SL3730-6TE41-1xU3 2 x 817 A 0.9 2 0
Table 5- 5 Factory setting of the overcurrent release on Line Connection Modules for Active Line Modules
Order number
Line Connection
Module
Order number
Active Line Module
Input current
Line Module
Short-time de-
layed short-
circuit release
(S)
Delay time short-
circuit release
(t
sd
)
6SL3700-0LG42-5BU3 6SL3730-7TG41-3xU3 2 x 1206 A 1.0 2 0
Property damage due to incorrect setting of the overcurrent release
Incorrect settings can cause unwanted or delayed tripping of the circuit breaker and result
in excessive damage to the cabinet unit.
• Check the above-indicated settings and, if necessary, adapt the settings to the system
configuration.