Cabinet Modules
5.4 Active Line Modules including Active Interface Modules
Cabinet Modules NEMA
194 Manual, 04/2014, A5E03586450A
Table 5- 23 Technical specifications for Active Line Modules (including Active Interface Module), 380 to 480 V 3 ph. AC,
part I
- Attached to Line Connection Module on left side
- for I
N DC
(50 Hz 400 V)
- for I
H DC
(50 Hz 400 V)
- for I
N DC
(60 Hz 460 V)
- for I
H DC
(60 Hz 460 V)
kW
kW
HP
132
115
200
160
145
250
235
210
400
300
270
500
- Rated current I
N DC
- Base load current I
H DC
1)
max DC
A
A
235
209
291
259
425
378
549
489
- Rated current I
N E
A
210
260
380
490
- auxiliary supply 24 V DC
- 400 V AC at 50 / 60 Hz
2)
2)
A
A
1.27
0.63 / 0.95
1.27
1.13 / 1.7
1.52
1.8 / 2.7
1.52
1.8 / 2.7
- Active Line Module
µF
4200
5200
7800
9600
3)
- at 50 Hz 400 V
- at 60 Hz 460 V
kW
kW
4.3
4.4
4.9
5.1
6.9
7.2
8.7
9.0
cfm
3
996
996
1759
1759
Sound pressure level L
pA
(1 m) at 50/60 Hz
4)
- Busbar cross-section
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
mm
2
PE busbar
600
240
5)
- Shielded
- Unshielded
- Shielded
ft
ft
m
8910
13300
2700
8910
13300
2700
8910
13300
2700
8910
13300
2700
Degree of protection (standard model)
(standard model, IP20)
- width
- height
6)
- depth
- width
- height
6)
inch
inch
inch
mm
mm
31.6
86.6
23.6
800
2200
31.6
86.6
23.6
800
2200
31.6
86.6
23.6
800
2200
31.6
86.6
23.6
800
2200