Cabinet Modules
5.2 Basic Line Modules
Cabinet Modules NEMA
162 Manual, 04/2014, A5E03586450A
Table 5- 15 Technical specifications for Basic Line Modules, 380 to 480 V 3 ph. AC
- Attached to Line Connection Module on left
--
--
--
...-2CU3
...-5CU3
...-8CU3
- for I
N DC
(50 Hz 400 V)
- for I
H DC
(50 Hz 400 V)
- for I
N DC
(60 Hz 460 V)
- for I
H DC
(60 Hz 460 V)
kW
kW
HP
200
160
305
250
200
380
400
315
585
560
450
855
710
560
1070
900
705
1340
- Rated current I
N DC
- Base load current I
H DC
1)
max DC
A
A
420
328
530
413
820
640
1200
936
1500
1170
1880
1467
- Rated current I
N E
A
365
460
710
1010
1265
1630
- Auxiliary supply 24 V DC
2)
A
1.1
- Basic Line Module
µF
7200
9600
14600
23200
29000
34800
3)
- at 50 Hz 400 V
kW
1.9
2.1
3.2
4.6
5.5
6.9
cfm
3
360
360
360
763
763
763
Sound pressure level L
pA
(1 m) at 50/60 Hz
- Busbar cross-section
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
mm
2
PE busbar
600
240
4)
- Shielded
- Unshielded
- Shielded
ft
ft
m
8580
12870
2600
8580
12870
2600
8580
12870
2600
13200
19980
4000
13200
19980
4000
13200
19800
4000
Degree of protection (standard model)
(standard model, IP20)
- width
- height
5)
- depth
- width
- height
5)
inch
inch
inch
mm
mm
15.8
86.6
23.6
400
2200
15.8
86.6
23.6
400
2200
15.8
86.6
23.6
400
2200
15.8/23.6
86.6
23.6
400/600
2200