22-75 Short Cycle Protection
Option: Function:
[0] * Disabled Timer set in par. 22-76
Interval between Starts is disabled.
[1] Enabled Timer set in par. 22-76
Interval between Starts is enabled.
22-76 Interval between Starts
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant] Sets the time desired as minimum time between two starts. Any normal
start command (Start/Jog/Freeze) will be disregarded until the timer has
expired.
22-77 Minimum Run Time
Range: Function:
0 s* [Application dependant] Sets the time desired as minimum run time after a normal start command
(Start/Jog/Freeze). Any normal stop command will be disregarded until
the set time has expired. The timer will start counting following a normal
start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock
command.
Does not work in cascade mode.