Initialization to Default Settings
There are two ways to initialize the frequency converter to default: Recommended initialization and manual
initialization.
Please be aware that they have different impact according to the below description.
Recommended initialization (via par. 14-22
Opera-
tion Mode)
1. Select par. 14-22
Operation Mode
2. Press [OK]
3. Select “Initialization”
4. Press [OK]
5. Remove power to unit and wait for display to turn
off.
6. Reconnect power and the frequency converter is
reset. Note that first start-up takes a few more
seconds
7. Press [Reset]
Par. 14-22
Operation Mode initializes all except:
Par. 14-50
RFI Filter
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Max Response Delay
Par. 8-37
Maximum Inter-Char Delay
Par. 15-00
Operating Hours to par. 15-05 Over
Volt's
Par. 15-20
Historic Log: Event to par. 15-22 His-
toric Log: Time
Par. 15-30
Alarm Log: Error Code to
par. 15-32
Alarm Log: Time
Parameters selected in par. 0-25 My Personal Menu, will stay present, with default factory setting.
Manual initialization
When carrying out manual initialization, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
My Personal Menu.
1. Disconnect from mains and wait until the dis-
play turns off.
2a. Press [Status] - [Main Menu] - [OK] at the
same time while power up for Graphical LCP
(GLCP)
3. Release the keys after 5 s
4. The frequency converter is now programd ac-
cording to default settings
This parameter initializes all except:
Par. 15-00
Operating Hours
Par. 15-03
Power Up's
Par. 15-04
Over Temp's
Par. 15-05
Over Volt's
How to Operate the Frequency Converter
5-12 BAS-SVX19C-EN