2-00 DC Hold/Preheat Current
Range: Function:
50 %* [Application dependant] Enter a value for holding current as a percentage of the rated motor cur-
rent I
M,N
set in par. 1-24 Motor Current. 100% DC holding current corre-
sponds to I
M,N
.
This parameter holds the motor (holding torque) or pre-heats the motor.
This parameter is active if [1] DC hold/Preheat is selected in
par. 1-80
Function at Stop.
The maximum value depends on the rated motor current.
Avoid 100 % current for too long. It may damage the motor.
2-16 AC brake Max. Current
Range: Function:
100.0
%*
[Application dependant] Enter the maximum permissible current when using AC brake to avoid
overheating of motor windings. The AC brake function is available in Flux
mode only.
2-17 Over-voltage Control
Option: Function:
Over-voltage control (OVC) reduces the risk of the frequency converter
tripping due to an over voltage on the DC link caused by generative pow-
er from the load.
[0] Disabled No OVC required.
[2] * Enabled Activates OVC.
The ramp time is automatically adjusted to avoid tripping of the frequency converter.
3-02 Minimum Reference
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant] Enter the Minimum Reference. The Minimum Reference is the lowest
value obtainable by summing all references. The Minimum Reference
value and unit matches the configuration choice made in par. 1-00
Con-
figuration Mode and par. 20-12 Reference/Feedback Unit, respectively.
This parameter is used in open loop only.
3-03 Maximum Reference
Range: Function:
Applica-
tion de-
pend-
ent*
[Application dependant] Enter the maximum acceptable value for the remote reference. The Max-
imum Reference value and unit matches the configuration choice made
in par. 1-00
Configuration Mode and par. 20-12 Reference/Feedback
Unit, respectively.
If operating with par. 1-00
Configuration Mode set for Closed Loop [3],
par. 20-14
Maximum Reference/Feedb. must be used.