Fuse Replacement Table
Drive Rating TR200
HP kW 208-230V 460-480V 575-600V
1.5 1.1 LP-CC-10 10A, 600V Class CC LP-CC-6 6A, 600V, Class CC LP-CC-5 5A, 600V, Class CC
2 1.5 LP-CC-15 15A, 600V Class CC LP-CC-10 10A, 600V, Class CC LP-CC-10 10A, 600V, Class CC
3 2.2 LP-CC-20 20A, 600V Class CC LP-CC-10 10A, 600V, Class CC LP-CC-10 10A, 600V, Class CC
5 3.7/4 LP-CC-30 30A, 600V Class CC LP-CC-20 20A, 600V, Class CC LP-CC-20 20A, 600V, Class CC
7.5 5.5 JJN-50 50A, 300V, Class T LP-CC-25 25A, 600V, Class CC LP-CC-25 25A, 600V, Class CC
10 7.5 JJN-50 50A, 300V, Class T LP-CC-30 30A, 600V, Class CC LP-CC-30 30A, 600V, Class CC
15 11 JJN-60 60A, 300V, Class T JJS-40 40A, 600V, Class T JJS-35 35A 600V Class T
20 15 JJN-80 80A, 300V, Class T JJS-40 40A, 600V, Class T JJS-35 35A 600V Class T
25 18.5 JJN-125 125A, 300V, Class T JJS-50 50A, 600V, Class T JJS-45 45A 600V Class T
30 22 JJN-125 125A, 300V, Class T JJS-60 60A, 600V, Class T JJS-50 50A 600V Class T
40 30 FWX-150A 150A, 250V JJS-80 80A, 600V, Class T JJS-60 60A 600V Class T
50 37 FWX-200A 200A, 250V JJS-100 100A, 600V, Class T JJS-80 80A 600V Class T
60 45 FWX-250A 250A, 250V JJS-125 125A, 600V, Class T JJS-100 100A 600V Class T
75 55 n/a JJS-150 150A, 600V, Class T JJS-125 125A 600V Class T
100 75 n/a FWH-200B 200A, 500V JJS-150 150A 600V Class T
125 90 n/a FWH-250A 250A, 500V JJS-175 175A 600V Class T
How to Connect
Cables General
For the TR200 High Power series mains and motor connections, please see TR200
High Power Operating Instruc-
tions
.
Cables General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
(60/75 °C) conductors are recommended.
Electrical Installation
4-4 BAS-SVX19C-EN