6-00 Live Zero Timeout Time
Range: Function:
10 s* [1 - 99 s] Enter the Live Zero Time-out time period. Live Zero Time-out Time is
active for analog inputs, i.e. terminal 53 or terminal 54, used as reference
or feedback sources. If the reference signal value associated with the
selected current input falls below 50% of the value set in par. 6-10
Ter-
minal 53 Low Voltage, par. 6-12 Terminal 53 Low Current, par. 6-20 Ter-
minal 54 Low Voltage or par. 6-22 Terminal 54 Low Current for a time
period longer than the time set in par. 6-00
Live Zero Timeout Time, the
function selected in par. 6-01
Live Zero Timeout Function will be activa-
ted.
6-01 Live Zero Timeout Function
Option: Function:
Select the time-out function. The function set in par. 6-01
Live Zero Time-
out Function will be activated if the input signal on terminal 53 or 54 is
below 50% of the value in par. 6-10
Terminal 53 Low Voltage,
par. 6-12
Terminal 53 Low Current, par. 6-20 Terminal 54 Low Voltage or
par. 6-22
Terminal 54 Low Current for a time period defined in
par. 6-00
Live Zero Timeout Time. If several time-outs occur simultane-
ously, the frequency converter prioritises the time-out functions as fol-
lows:
1. Par. 6-01
Live Zero Timeout Function
2. Par. 8-04
Control Timeout Function
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
[0] * Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
How to program the Frequency Converter
6-36 BAS-SVX19C-EN