EasyManua.ls Logo

Trane TR200 - Troubleshooting; Alarms and Warnings

Trane TR200
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
Alarms and Warnings
A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by
a code on the display.
A warning remains active until its cause is no longer present. Under certain circumstances operation of the
motor may still be continued. Warning messages may be critical, but are not necessarily so.
In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation
once their cause has been rectified.
This may be done in four ways:
1. By using the [RESET] control button on the keypad.
2. Via a digital input with the “Reset” function.
3. Via serial communication/optional fieldbus.
4. By resetting automatically using the [Auto Reset] function, which is a default setting for TR200 Drive, see
par. 14-20
Reset Mode in the TR200 Programming Guide
After a manual reset using the [RESET] button on the keypad, the [AUTO ON] or [HAND ON] button must be pressed
to restart the motor.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked
(see also table on following page).
Alarms that are trip-locked offer additional protection, means that the mains supply must be switched off before the
alarm can be reset. After being switched back on, the frequency converter is no longer blocked and may be reset as
described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in par. 14-20
Reset Mode (Warning:
automatic wake-up is possible!)
If a warning and alarm is marked against a code in the table on the following page, this means that either a warning
occurs before an alarm, or it can be specified whether it is a warning or an alarm that is to be displayed for a given fault.
This is possible, for instance, in par. 1-90
Motor Thermal Protection. After an alarm or trip, the motor carries on coasting,
and the alarm and warning flash on the frequency converter. Once the problem has been rectified, only the alarm
continues flashing.
Alarms that are trip-locked offer additional protection, means that the mains supply must be switched off before
the alarm can be reset. After being switched back on, the frequency converter is no longer blocked and may be
reset as described above once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in par. 14-20
Reset Mode
Automatic wake-up is possible!
Could result in equipment or property damage.
If a warning and alarm is marked against a code in the table on the following page, this means that either a
warning occurs before an alarm, or it can be specified whether it is a warning or an alarm that is to be displayed
for a given fault.
BAS-SVX19C-EN 7-1

Table of Contents

Other manuals for Trane TR200

Related product manuals