WARNING
In motors without phase insulation paper or other insulation reinforcement suitable for operation with voltage supply
(such as a frequency converter), fit a sine-wave filter on the output of the frequency converter. (Motors that comply
with IEC 60034-17 do not require a Sine-wave filter) failure to do so could result in equipment damage.
No. 96 97 98 Motor voltage 0-100% of mains voltage.
U V W 3 cables out of motor
U1 V1 W1
6 cables out of motor, Delta-connected
W2 U2 V2
U1 V1 W1 6 cables out of motor, Star-connected
U2, V2, W2 to be interconnected separately
(optional terminal block)
No. 99 Earth connection
PE
Table 4. 8: 3 and 6 cable motor connection.
Electrical Installation
BAS-SVX19C-EN 4-19