• Set-up select lsb - Set-up select msb
• Stop command from serial communication
• Quick stop
•DC brake
External stop signals activated by means of control signals or a serial bus will override a “start” command via the
keypad.
[Off]
stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. 0-41
[Off] Key on LCP.
If no external stop function is selected and the [Off] key is inactive the motor can only be stopped by discon-
necting the mains supply.
[Auto on]
enables the frequency converter to be controlled via the control terminals and/or serial communication. When
a start signal is applied on the control terminals and/or the bus, the frequency converter will start. The key can
be selected as Enable [1] or Disable [0] via par. 0-42
[Auto on] Key on LCP.
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand on] – [Auto on].
[Reset]
is used for resetting the frequency converter after an alarm (trip). It can be selected as
Enable
[1] or
Disable
[0]
via par. 0-43
[Reset] Key on LCP.
The parameter shortcut can be carried out by holding down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.
How to Operate the Frequency Converter
BAS-SVX19C-EN 5-7