D300529 0115 - BL67 I/O modules
12-35
BL67-1SSI
SSI_STS3 0 These four bits transfer the status bits of the SSI encoder
with the status messages of the SSI module. With some SSI
encoders, the status bits are transferred together with the
position value.
1
SSI_STS2 0
1
SSI_STS1 0
1
SSI_STS0 0
1
REG_RD_ABORT 0 The reading of the register defined in REG_RD_ADR has
been accepted and executed. The content of the register
can be found in the user data (REG_RD_DATA, byte 0-3).
1 Reading of the register defined in REG_RD_ADR has not
been accepted. The user data range (REG_RD_DATA Bytes
0-3) is zero.
REG_RD_ADR 0…63 Address of the register to be read. If the read operation is
successful (REG_RD_ABORT = 0), the user data is located in
REG_RD_DATA of the process input data (bytes 0 to 3).
REG_RD_DATA 0 bis
2
32
-1
Content of the register to be read if REG_RD_ABORT=0.
If REG_RD_ABORT =1, then REG_RD_DATA=0.
Table 12-1:
Meaning of the
data bits (process
input)
Designation Value Description