T2-03: PM Motor Type
Selects the type of PM motor the drive will operate.
No. Name Setting Range Default
T2-03 PM Motor Type 0, 1 1
Setting 0: IPM motor
Setting 1: SPM motor
n
T2-04: PM Motor Rated Power
Specifies the motor rated power in kilowatts.
No. Name Setting Range Default
T2-04 PM Motor Rated Power 0.00 to 650.00 kW
Determined by o2-04
and C6-01
n
T2-05: PM Motor Rated Voltage
Sets the motor rated voltage.
No. Name Setting Range Default
T2-05 PM Motor Rated Voltage
0.0 to 255.0 V
<1>
200.0 V
<1>
<1> Value shown is specific to 200 V class drives. Double value for 400 V class drives.
n
T2-06: PM Motor Rated Current
Enter the motor rated current in amps.
No. Name Setting Range Default
T2-06 PM Motor Rated Current
0.0% to 300.0% of the
drive rated current.
Determined by o2-04
n
T2-07: PM Motor Base Frequency
Enter the motor base frequency in Hz.
Note: T2-07 will be displayed when in OLV/PM.
No. Name Setting Range Default
T2-07 PM Motor Base Frequency 0.0 to 240.0 Hz 87.5 Hz
n
T2-08: Number of PM Motor Poles
Enter the number of motor poles.
No. Name Setting Range Default
T2-08 Number of PM Motor Poles 2 to 48 6
n
T2-10: PM Motor Stator Resistance
Enter the motor stator resistance per motor phase.
No. Name Setting Range Default
T2-10 PM Motor Stator Resistance 0.000 to 65.000 Ω Determined by T2-02
n
T2-11: PM Motor d-Axis Inductance
Enter the d-Axis inductance per motor phase.
No. Name Setting Range Default
T2-11 PM Motor d-Axis Inductance 0.00 to 600.00 mH Determined by T2-02
4.8 Auto-Tuning