5.2 Motor Performance Fine-Tuning
This section offers helpful information for counteracting oscillation, hunting, and other problems that occur while performing
a trial run. Refer to the appropriate control method in this section.
Note: This section describes commonly edited parameters that may be set incorrectly. Consult Yaskawa for more information on detailed settings
and for fine-tuning the drive.
u
Fine-Tuning V/f Control
Table 5.1 Parameters for Fine-Tuning Performance in V/f
Problem Parameter No. Corrective Action Default
Suggested
Setting
Motor hunting and
oscillation at speeds
between 10 and 40 Hz
Hunting Prevention Gain
(n1-02)
Reduce the setting if insufficient motor torque relative to the size
of the load causes hunting.
Increase the setting when motor hunting and oscillation occur
with a light load.
Reduce the setting if hunting occurs when using a motor with a
relatively low inductance, such as a high-frequency motor or a
motor with a larger frame size.
1.00 0.10 to 2.00
Motor noise
Motor hunting and
oscillation at speeds up
to 40 Hz
Carrier Frequency
Selection (C6-02)
Increase the carrier frequency If the motor noise is too loud.
Lower the carrier frequency when motor hunting and oscillation
occur at speeds up to 40 Hz.
The default setting for the carrier frequency depends on the drive
capacity (o2-04).
1 (2 kHz)
<1>
1 to max. setting
Poor torque or speed
response
Motor hunting and
oscillation
Torque Compensation
Primary Delay Time
(C4-02)
Reduce the setting if motor torque and speed response are too
slow.
Increase the setting if motor hunting and oscillation occur.
Depends on
o2-04, Drive
Model
Selection
100 to 1000 ms
Poor motor torque at
speeds below 10 Hz
Motor hunting and
oscillation
Torque Compensation
Gain (C4-01)
Increase the setting if motor torque is insufficient at speeds
below 10 Hz.
Reduce the setting if motor hunting and oscillation with a
relatively light load.
1.00 0.50 to 1.50
Poor motor torque at
low speeds
Motor instability at
motor start
Mid Output Voltage A
(E1-08)
Minimum Output
Voltage (E1-10)
Increase the setting if motor torque is insufficient at speeds
below 10 Hz.
Reduce the setting If motor instability occurs at motor start.
Depends on
A1-02,
E1-03, and
o2-04
Default setting
±5 V
<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.