B.6 F: Communication Option Parameters
u
F6, F7: Communication Option Card
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKS
options. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.
No.
(Addr.
Hex)
Name LCD Display Description Values Page
F6-01
(3A2)
Communications Error
Operation Selection
Comm Bus Flt Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm (d1-04)
5: Alarm (C1-02)
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
<1>
4: Alarm only. Continue operation using the frequency
reference set in d1-04.
<1> <2>
5: Alarm only. Decelerate to stop using the deceleration time
in C1-02.
<3> <4>
Default: 1
Range: 0 to 5
F6-02
(3A3)
External Fault from
Comm. Option
Detection Selection
EF0 Detection
0: Always Detected
1: Only During Run
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1
F6-03
(3A4)
External Fault from
Comm. Option
Operation Selection
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
<1>
Default: 1
Range: 0 to 3
F6-06
(3A7)
Torque Reference/
Torque Limit Selection
from Comm. Option
Torq Ref/Lmt Sel
0: Disabled
1: Enabled
OLV/PMOLV/PM
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled. Torque reference/limit from option board enabled.
Default: 0
Range: 0, 1
F6-07
(3A8)
Multi-Step Speed
Enable/Disable
Selection when NefRef/
ComRef is Selected
Fref PrioritySel
0: Net/Com REF
1: MultiStep Speed
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7) Default: 0
Range: 0, 1
F6-08
(36A)
<5>
Reset Communication
Parameters
Com Prm Init Sel
0: Init Com Prms
1: No Init Com Prms
0: Communication-related parameters (F6-oo) are not reset
when the drive is initialized using A1-03.
1: Reset all communication-related parameters (F6-oo) when
the drive is initialized using A1-03.
Default: 0
Range: 0, 1
F6-14
(03BB)
CC-Link bUS Error
Auto Reset
Bus Err Auto Rst
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-46
(02FC)
BACnet Baud Rate
BAC Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
<3>
7: 76800
<3>
8: 115200
<3>
Default: 3
Range: 0 to 8
F7-01
(3E5)
<6> <7>
<8>
IP Address 1 IP Address 1 Sets the most significant octet of network static IP address.
Default: 192
Min.: 0
Max.: 255
F7-02
(3E6)
<6> <7>
<8>
IP Address 2 IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Min.: 0
Max.: 255
F7-03
(3E7)
<6> <7>
<8>
IP Address 3 IP Address 3 Sets the third most significant octet of network static IP address.
Default: 1
Min.: 0
Max.: 255
B.6 F: Communication Option Parameters
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
299
B
Parameter List

Table of Contents