4.13 Advanced Drive Setup Adjustments
This section explains advanced settings and parameters that may be required for drive operation. Refer to Parameter List on
page 281 for a complete listing of drive parameters if more information is required for parameters not listed in this section
or in 4.7 Basic Drive Setup Adjustments.
n
A1-00: Language Selection
Selects the display language for the HOA keypad.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No. Parameter Name Setting Range Default
A1-00 Language Selection 0, 1, 3, 5, 6 0
Setting 0: English
Setting 1: Japanese
Setting 3: French
Setting 5: Spanish
Setting 6: Portuguese
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 2 2
Setting 0: Operation Only
A1-01, A1-04, and Drive Mode can be accessed and set. All U monitor parameters can be accessed. Parameters that are set
in A2-01 to A2-32 can be accessed in Setup Mode. Verify Mode, Setup Mode, and Auto-Tuning Mode cannot be accessed.
Setting 1: User Parameters
A1-00, A1-01, A1-04, and Drive Mode can be accessed and set. All U monitor parameters can be accessed. Parameters that
are set in A2-01 through A2-32 can be accessed in Setup Mode. Verify Mode and Auto-Tuning Mode cannot be accessed.
Setting 2: Advanced Access Level (A)
All parameters can be viewed and edited.
Notes on Parameter Access
If the drive parameters are password protected by A1-04 and A1-05, parameters A1-01 through A1-03, A1-07, and A2-01
through A2-32 cannot be modified.
If a digital input terminal programmed for “Program lockout” (H1-oo = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
HOA keypad until an Enter command is issued to the drive from the serial communication.
4.13 Advanced Drive Setup Adjustments
156
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual

Table of Contents

Other manuals for YASKAWA Z1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 and is the answer not in the manual?

YASKAWA Z1000 Specifications

General IconGeneral
ModelZ1000
CategoryController
Humidity95% RH or less (non-condensing)
Control MethodV/F Control
Frequency Range400 Hz
ProtectionOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus
Operating Temperature-10 to 50°C
Storage Temperature-20 to 60°C
AltitudeUp to 1000 meters without derating
Cooling MethodForced Air
Enclosure RatingIP20
Voltage Class200V, 400V