n
H5-14, H5-15: BACnet Device Object Identifiers 0 and 1
These parameters set the Instance Identifier of the BACnet Device Object, where the H5-14 value is the least significant word
and the H5-15 value is the most significant word.
No. Name Setting Range Default
H5-14 BACnet Device Object Identifier 0 0 to FFFFH 1
H5-15 BACnet Device Object Identifier 1 0 to 3FH 0
Example 1: Set Device Object Instance Identifier of “1234”
1234 decimal is equal to 4D2H (hexadecimal)
Set H5-14 to 4D2H and set H5-15 to 0.
Example 2: Set Device Object Instance Identifier of “1234567”
12334567 decimal is equal to 12D687H
Set H5-14 to D687H and set H5-15 to 12H.
C.4 BACnet Setup Parameters
YASKAWA ELECTRIC TOEP C710616 45F YASKAWA AC Drive – Z1000 User Manual
349
C
BACnet
Communications

Table of Contents