CascadeSecondary-loopPositionProportionalControlFunctionBlockDiagram
Target setpoints 1 to 8
AUTO, MANCAS
SP ramp rate
SP limiter
PV input
DI16PV RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
A.BS
A.FL
BS
FL
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
10-seg. linearizer approx./bias
PMD An, Bn
CNT ALG
UPR, DNR TMU
SPNO SP
SPH, SPL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
A.BS
A.FL
A.SR A.LC
UNIT
IN
RH, RL SDP SH, SL
Equipped as standard
DI3DI2DI1
Control computation
Ratio bias computation
RT RBS
Remote input filter
RFL
Manual operation
Input error preset output
Preset output
AUTO
When sensor
burnout occurs
Normal
MAN
RUNSTOP
Output limiter
EPO
OH, OL
PO
S/R
Signal comparison
Feedback input
Direct/reverse signal
Valve position sliding
resistor or current
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standard Equipped as standard
Current
LPS
24 V loop
power supply
Current
OUT RET
PMD
OU.H
HYS
DB
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD An, Bn
Split computation
10-seg. linearizer approx./bias
OUT
retransmission output
O1RS
Target setpoint output
RTS
A/M
(ON in AUT, MAN, and STOP)
Equipped as standard Equipped as standard
AL3AL2AL1
Tracking
switch
Alarm Tracking switch
(to Loop-1 controller)
(to Loop-1 controller)
Cascade input
(from Loop-1 controller)
Contact inputs
(from Loop-1 controller)
H relay
( key)
L relay
( key)
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
In Estimating-type position proportional control, the limiter function
does not work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
In Manual operation, the relay turns on while the
or key is pressed. Output limiter does not work.
Cascade (OFF→ON)
Automatic (OFF→ON)
Manual (OFF→ON)
PV display SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
Switch from CAS (contact ON) to AUTO (contact
OFF) at FAIL of Loop-1 controller
Position Proportional Computation Output cannot be calculated by ladder program.
Universal input (E1-terminal area) can be used
when UT55A/UT52A optional suffix code /U1.
However, DI16 does not exist.
(For Standard model)
Cascade input can be used when UT55A suffix code: Type
2 = 1, 2, 4, 5, or 7; UT52A suffix code: Type 2 = 1 or 2.
(For Detailed model)
Cascade input can be used when UT55A/UT52A optional
suffix code /R1 or /RCH1.
(For Standard model)
DI16 is equipped when UT55A suffix code: Type 2 = 1, 2,
4, 5, or 7; UT52A suffix code: Type 2 = 1 or 2.
(For Detailed model)
DI16 is equipped when UT55A/UT52A optional suffix code
/R1 or /RCH1.